Manufactured by:<br />

<strong>MV</strong> <strong>Switchgear</strong> Secondary<br />

Distribution Networks<br />

Fully Gas-Insulated Modular and Compact (RMU)<br />

System Up to 36 kV<br />

BO-<strong>CGM</strong>.3/3<br />

SMART RMU <strong>Switchgear</strong> in Metro Manila<br />

• Protection and safety for people, goods and equipment against internal<br />

arc effects, proven through test performed in accordance with IEC<br />

62271-200 standard.<br />

• Capable of withstanding harsh environmental conditions (including<br />

flooding), long service life and absence of maintenance in live parts<br />

through full gas insulation and the use of screened connectors.<br />

• Full modularity and future extensibility in both directions through the<br />

use of connecting set. Flexibility to configure all types of diagram.<br />

pazifik<br />

power<br />

• Smaller size and lower weight, making handling and installation easier.<br />

• Safe and simple operation through the use of user-friendly driving<br />

mechanisms, including interlocks as standard.<br />

www.ppi.ph


General Description<br />

Consists of a wide range of SF 6 fully insulated compact, modular<br />

cubicles enabling the configuration of any electrical diagram in<br />

Medium Voltage Secondary Distribution networks up to 36kV.<br />

This development brings a highly safe, reliable and user-friendly<br />

assembly, capable of withstanding all environmental conditions.<br />

The performance of routine test across the various phases of<br />

the assembly procedure and the use of the most innovative<br />

manufacturing techniques assure the highest level of quality, as<br />

reflected in its ISO 9001 certification.<br />

Features<br />

• Protection and safety for people, goods and equipment<br />

against internal arc effects, proven through test performed in<br />

accordance with IEC 62271-200 standard.<br />

• Capable of withstanding harsh environmental conditions<br />

(including flooding), long service life and absence of<br />

maintenance in live parts through full gas insulation and the<br />

use of screened connectors.<br />

• Full modularity and future extensibility in both directions<br />

through compact connecting set. Flexibility to configure all<br />

types of diagram with the use of a connecting set.<br />

• Smaller size and lower weight, making handling and<br />

installation easier.<br />

• Safe and simple operation through the use of user-friendly<br />

driving mechanisms, including interlocks as standard.<br />

• Extra safety: incorporation, a light voltage presence indicator;<br />

and optionally, an acoustic alarm preventing earthing.<br />

• Accessories and live testing as an option.<br />

• Horizontal fuse holders with front access, protected within a<br />

gas tank.<br />

• Easy cable connection through front plug-in or screwable<br />

terminals.<br />

Environmentally-friendly:<br />

• Use of highly recyclable materials.<br />

• Minimal gas volume per functional unit.<br />

• End-of-life product management.<br />

Standards<br />

IEC 62271-1<br />

Common specifications for high-voltage switchgear and<br />

controlgear standards.<br />

IEC 62271-200<br />

Alternating current metal-enclosed switchgear and controlgear<br />

for rated voltages above 1kV and up to and including 52kV.<br />

IEC 60265-1<br />

High-voltage switches. Part 1: High voltage switches for rated<br />

voltages above 1kV and less than 52kV.<br />

IEC 62271-102<br />

Alternating current disconnectors and earthing switches.<br />

IEC 62271-105<br />

High voltage alternating current switch-fuse combinations.<br />

IEC 62271-100<br />

High voltage alternating current circuit-breakers.<br />

IEC 60255<br />

Electrical relays.<br />

IEC 60529<br />

Degrees of protection provided by enclosures.<br />

IEC 61958<br />

Voltage presence indicating systems.<br />

The Fully Gas-Insulated Modular and Compact (RMU) System<br />

meets the immersion test at 3 meters water column pressure,<br />

24 hours at rated voltage and insulating test at power<br />

frequency.


Types of Modules<br />

Incoming feeder<br />

or line functional<br />

unit.<br />

Fused-protection<br />

functional unit<br />

Vacuum circuit<br />

breaker protection<br />

functional unit,<br />

with or without<br />

recloser (RAV<br />

or AV driving<br />

mechanism).<br />

Busbar switch<br />

functional unit<br />

Busbar switch<br />

with earthing<br />

unit.<br />

Metering<br />

functional<br />

unit (different<br />

configuration)<br />

Cable rising<br />

functional unit.<br />

Busbar rising<br />

functional unit.<br />

Compact cubicle with two feeder and one<br />

fused-protection functional units (RMU type).<br />

Technical Characteristics<br />

Fully Gas-Insulated Modular and Compact (RMU) System<br />

L P V(AV) V(RAV) S S-Pt M RC RB 2LP<br />

Rated Voltage (kV) 36<br />

Rated Current (A)<br />

Busbars 400/630<br />

Outgoing 400/630 200 400/630 400/630 - - - 400/630 400/630 400/630(L)<br />

200(P)<br />

Short-time<br />

16/20* 16/20* 16/20* 16/20* 16/20* 16/20* - - 16/20* 16/20*<br />

current (kA 1/3s)<br />

Insulation level:<br />

Power Frequency (kV) 70/80 70/80 70/80 70/80 70/80 70/80 70/80 - 70/80 70/80<br />

Lightning<br />

170/195 170/195 170/195 170/195 170/195 170/195 170/195 - 170/195 170/195<br />

impulse (kV) PEAK<br />

Rated-frequency (Hz) 50/60**<br />

IP rate<br />

General<br />

IP2XD<br />

Gastank and fuse holders<br />

IPX8<br />

Physical Characteristics L P V(AV) V(RAV) S S-Pt M RC RB 2LP<br />

Height (mm) 1745 1745 1745 1800 1745 1745 1950 1745 1745 1745<br />

Width (mm) 418 480 600 600 418 600 900/1100 368 418 1316<br />

Depth (mm) 845 1010 850 850 845 845 1160 831 850 1027<br />

Weight (kg) # 138 211 240 240 135 175 290* 42 138 421<br />

(*) Test performed at 21 kA.<br />

(**) Values represented at 50Hz, for other frequencies please contact our technical-Commercial Department.<br />

(#) Without relays, motor driving mechanisms and transformers.


Modularity.<br />

The extensible cubicles have side female bushing to<br />

connect the main busbars through this connecting<br />

set. This allows current to flow, while controlling<br />

the electric field by means of insulating elastomer<br />

layers, free of partial discharges.<br />

Thanks to the design of the connecting set, an<br />

internal equipotential area is created. Here a number<br />

of contacts are distributed in a circle for connection<br />

to the female bushings.<br />

A reliable, strong electrical continuity is therefore<br />

achieved, even when exposed to a short-circuit<br />

current. The connecting set also maintains all<br />

operational features of the cubicles.<br />

While the installation is not being extended, the extensible<br />

cubicles have removable sealing elements for the female<br />

bushings.<br />

The cubicle connecting procedure stands out for its ease and speed of on-site<br />

installation, including in Transformer Substations with uneven floors.<br />

The modularity and extensibility of the system ensure maximum flexibility to<br />

configure any kind of medium voltage electrical diagram.<br />

Applications<br />

Used for a wide variety of facilities, both public and private its<br />

main applications are:<br />

• Utility transformer substations.<br />

• Private transformer substations.<br />

• Switching substations.<br />

• Remote controlled substations.<br />

• Infrastructures.<br />

• Industrial facilities<br />

• Wind farms.<br />

• Photovoltaic facilities.<br />

• Co-generation facilities<br />

• etc.<br />

Public Application<br />

Private Application


Safety<br />

• Personal, goods and equipment protection against the effects<br />

of internal arcs.<br />

• Capability of withstanding harsh environmental conditions<br />

(humidity, salinity, dust, pollution, etc.) and protection against<br />

indirect contacts.<br />

• The leak-proof and sealed steel gas tank, houses the breaking<br />

and switching components.<br />

• IP2XD IP rating of the cubicle assembly.<br />

• Voltage presence detection.<br />

• An acoustic alarm preventing earthing (as an option).<br />

• Front driving mechanisms that allow safe and simple<br />

operations.<br />

• Horizontal fuse holders with front access, protected within a<br />

gas tank.<br />

• Standard internal interlocks preventing improper operations,<br />

in accordance with IEC 62271-200 standard. Additional<br />

interlocks with padlock or lock, as an option.<br />

Reliability<br />

• Routine and traceability factory-testing in all equipments.<br />

• Interlocks between the switching and breaking components.<br />

• Visual display of the position of the switchgear in the synoptic<br />

diagram, validated by the kinematic chain test in accordance<br />

with IEC 62271-102.<br />

• High anti-corrosive levels achieved with the use of innovative<br />

materials.<br />

• Maintenance-free live parts.<br />

• Possibility of assembling accessories and performing test<br />

under voltage.<br />

Protection, Control and Automation<br />

Focusing on Medium Voltage, Ormazabal has a broad range of<br />

protection and automation applications and services capable of<br />

meeting the needs of any distribution network.<br />

Medium voltage cubicle-integrated units provide the idea<br />

solution for implementation in the most demanding of facilities,<br />

offering a high level of service in comparison with conventional<br />

system.<br />

Applications<br />

Protection<br />

• <strong>MV</strong> Customer Supplies<br />

• Protection for Switching and Private Industrial<br />

Substations<br />

• Rural TS (CTR) protection<br />

• Generator Set Protection<br />

• Substation Protection<br />

Automation and Remote Control<br />

• Remote Control<br />

• Automatic Transfers<br />

• Fault Detection<br />

• Acoustic voltage presence alarm<br />

• Secondary Switching Points<br />

• Easy cable connection, with plug-in or screwed connectors.<br />

Internal Arc<br />

The cubicles are designed to protect people and goods against<br />

the effect of internal arcs, complying with the criteria of IEC<br />

62271-200 standard, Appendix A:<br />

Gas tank internal arc: 16 kA 0,5 s / 20* kA 0,5s<br />

Gas tank internal arc: 16 kA 1s /20* kA1 s#<br />

IAC AFL Class: 16 kA 1 s / 20* kA 1 s#<br />

(*) Tests performed at 21 kA<br />

(#) Except for <strong>CGM</strong>.3-V with RAV mechanism.


Batteries that are robust energy<br />

storage solutions, with a proven<br />

technology that has been used for<br />

decades.<br />

(Sunlight, Greece)<br />

Disconnecting Switches<br />

15kV up to 800kV<br />

(Hapam, Netherlands)<br />

manage energy better<br />

Single HighPrecision Superstatic<br />

and Tamper Proof Meter<br />

(Landis+Gyr, Switzerland)<br />

scadaflex<br />

Substation Automation System<br />

A solution package for system<br />

integration, substation automation<br />

and energy management system.<br />

(SCADAFLEX, <strong>PPI</strong> Pazifik Power<br />

Inc., Phils.)<br />

®<br />

Instrument Transformers<br />

Our Power Your Confidence<br />

Instrument Transformers<br />

Dry-Type Resin Insulated Outdoor/Indoor<br />

Current Transformer<br />

and Potential Transformer<br />

(WTW, Germany)<br />

Fully Automatic Measurement of<br />

the dielectric strength of liquid<br />

insulators up to 100 kV.<br />

(BAUR, Austria)<br />

Modular UPS solutions in multiple<br />

capacity options<br />

(Gamatronics, Israel)<br />

Glass Fibre reinforced vacuum<br />

technology (GVT) for various<br />

applications<br />

(WTW, Germany)<br />

HORSTMANN<br />

GmbH<br />

Fully Electronic and Self-Adjusting<br />

Fault Circuit HORSTMANN Indicator<br />

(Horstmann, GmbH Germany)<br />

State of the art Meter Testing<br />

and Calibration Equipment and<br />

Instrument Test Set<br />

(MTE, Switzerland)<br />

TRIDELTA<br />

Protection of transformers,<br />

switch-gears and plants against<br />

atmospheric and switching<br />

overvoltages<br />

(Tridelta, Germany)<br />

pazifik<br />

power<br />

www.ppi.ph<br />

Turnkey Substation up to 100<strong>MV</strong>A<br />

(<strong>PPI</strong> Pazifik Power, Inc., Philippines)<br />

Efficient Electricity Solutions<br />

<strong>PPI</strong> is a company with more than twenty (20) years of successful operation in the Philippines.<br />

Over the years, it has developed and actively supplied an extensive and full power line of products and services from the best manufacturers in<br />

Europe. Among its most sought top of the line products are: Turnkey projects in the supply of substations with rated voltage of up to 230kV, electricity<br />

meters, meter test equipment, instrument transformers, power transformers, disconnectors, fault indicators, surge arresters, switchgears, oil<br />

testers, cable diagnostics, batteries, harmonic filters, and automation systems, among others.<br />

Our commitment to establish closer customer relationships make us understand your business needs and power solution requirements.<br />

MAKATI HEAD OFFICE<br />

4/F and 6/F, South Park Plaza, Santiago Street<br />

Paseo de Magallanes Commercial Center<br />

1232 Makati City, Metro Manila, Philippines<br />

CEBU BRANCH<br />

Unit 3 ASY Bldg. A.C. Cortes Ave.<br />

Mandaue City, Cebu, Philippines<br />

Tel.: +63 2 511 88 88 | Fax: +63 2 836 43 23<br />

E-mail: info@ppi.ph | Website: www.ppi.ph<br />

Facebook: www.facebook.com/PazifikPowerInc

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!