Solid Laminated Partitions<br />
DESCRIPTION<br />
Laminated Partitions have<br />
been developed for use<br />
where sturdy, nonloadbearing<br />
walls are desired.<br />
The total thickness is<br />
nominal 2". 1" Fire-Shield<br />
Shaftliner is used between<br />
face layers of gypsum<br />
board.<br />
PHYSICAL PROPERTIES<br />
A. Fire Resistance. Fire<br />
endurance ratings have<br />
been established by the<br />
following tests:<br />
FM WP 671 - 1 HOUR:<br />
1/2" Regular <strong>Gypsum</strong> face<br />
boards and ProForm Brand<br />
Sta-Smooth joint<br />
compound* as laminating<br />
compound.<br />
UL U505 - 2 HOUR:<br />
5/8" Type X Fire-Shield<br />
face boards and ProForm<br />
Brand Sta-Smooth joint<br />
compound* as laminating<br />
compound.<br />
UL U525 - 2 HOUR:<br />
1/2" Fire-Shield Type C<br />
face board and ProForm<br />
Brand Sta-Smooth<br />
compound* as laminating<br />
compound.<br />
UL U529 - 2 HOUR:<br />
1/2" Fire-Shield Type C<br />
face boards and ProForm<br />
Brand Sta-Smooth joint<br />
compound* as laminating<br />
compound.<br />
B. Sound Isolation. An STC<br />
rating of 34 has been<br />
achieved in tests conducted<br />
in accordance<br />
with ASTM E 90.<br />
TECHNICAL DATA<br />
Maximum Partition Length<br />
Ceiling Height Between Restraints<br />
12' (3658 mm) 14' (4267 mm)<br />
11' (3353 mm) 20' (6096 mm)<br />
10' (3048 mm) Over 20' (6096 mm)<br />
110 NATIONAL GYPSUM BOARD PRODUCTS<br />
C. Economical. The laminated<br />
partition offers a substantial<br />
saving in installation time<br />
and subsequently in labor<br />
costs over other types of<br />
solid partitions. The 1"<br />
gypsum core is quickly and<br />
easily installed and the<br />
large sheets of gypsum<br />
board provide a dry finish<br />
surface in minimum time.<br />
LIMITATIONS<br />
The laminated partition is<br />
adapted to any type of<br />
building for nonloadbearing<br />
partitions not<br />
exceeding 12' in height.<br />
Further limitations to height<br />
are based on the partition<br />
length in the table below.<br />
*Required for fire rating.<br />
JOINT<br />
COMPOUND<br />
ADHESIVE<br />
FLOOR LINE<br />
DETAILS<br />
GYPSUM BOARD CORNERBEAD<br />
CAULKING<br />
12d NAIL/12" O.C.<br />
1" FIRE-SHIELD SHAFTLINER<br />
TAPE AND JOINT<br />
COMPOUND<br />
1" FIRE-SHIELD SHAFTLINER<br />
GYPSUM BOARD<br />
CORNER WALL DETAIL<br />
09250U<br />
Scale: 3" = 1'-0"<br />
GYPSUM BOARD<br />
BASE<br />
VERTICAL SECTION USING<br />
METAL FLOOR RUNNER<br />
09250T<br />
Scale: 3" = 1'-0"<br />
1/4"<br />
L RUNNER<br />
1" FIRE-SHIELD<br />
SHAFTLINER<br />
L FLOOR<br />
RUNNER<br />
1" FIRE-SHIELD SHAFTLINER<br />
CASING BEAD<br />
ANCHORAGE TO CONCRETE<br />
CEILINGS, WALLS OR COLUMNS<br />
09250V<br />
Scale: 3" = 1'-0"