Network UPS Tools User Manual
Network UPS Tools User Manual
Network UPS Tools User Manual
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Network</strong> <strong>UPS</strong> <strong>Tools</strong> <strong>User</strong> <strong>Manual</strong> 55 / 84<br />
Name<br />
frequency<br />
frequency.nominal<br />
realpower<br />
power<br />
Description<br />
Frequency (Hz)<br />
Nominal frequency (Hz)<br />
Current value of real power (Watts)<br />
Current value of apparent power (Volt-Amps)<br />
C.1.6<br />
EXAMPLES<br />
Partial Three phase - Three phase example:<br />
input.phases: 3<br />
input.frequency: 50.0<br />
input.L1.current: 133.0<br />
input.bypass.L1-L2.voltage: 398.3<br />
output.phases: 3<br />
output.L1.power: 35700<br />
output.powerfactor: 0.82<br />
Partial Three phase - One phase example:<br />
input.phases: 3<br />
input.L2.current: 48.2<br />
input.N.current: 3.4<br />
input.L3-L1.voltage: 405.4<br />
input.frequency: 50.1<br />
output.phases: 1<br />
output.current: 244.2<br />
output.voltage: 120<br />
output.frequency.nominal: 60.0<br />
C.1.7<br />
battery: Any battery details<br />
Name Description Example value<br />
battery.charge Battery charge (percent) 100.0<br />
battery.charge.low<br />
Remaining battery level when <strong>UPS</strong> 20<br />
switches to LB (percent)<br />
battery.charge.restart<br />
Minimum battery level for <strong>UPS</strong> restart 20<br />
after power-off<br />
battery.charge.warning<br />
Battery level when <strong>UPS</strong> switches to 50<br />
"Warning" state (percent)<br />
battery.voltage Battery voltage (V) 24.84<br />
battery.voltage.nominal Nominal battery voltage (V) 024<br />
battery.voltage.low<br />
Minimum battery voltage, that triggers 21,52<br />
FSD status<br />
battery.voltage.high<br />
Maximum battery voltage (i.e. 26,9<br />
battery.charge = 100)<br />
battery.capacity Battery capacity (Ah) 7.2<br />
battery.current Battery current (A) 1.19<br />
battery.current.total Total battery current (A) 1.19<br />
battery.temperature Battery temperature (degrees C) 050.7<br />
battery.runtime Battery runtime (seconds) 1080<br />
battery.runtime.low<br />
Remaining battery runtime when <strong>UPS</strong> 180<br />
switches to LB (seconds)<br />
battery.runtime.restart<br />
Minimum battery runtime for <strong>UPS</strong><br />
restart after power-off (seconds)<br />
120