<strong>Network</strong> <strong>UPS</strong> <strong>Tools</strong> <strong>User</strong> <strong>Manual</strong> 52 / 84<br />

Name Description Example value<br />

ups.timer.reboot<br />

Time before the load will be rebooted 10<br />

(seconds)<br />

ups.timer.shutdown<br />

Time before the load will be shutdown 20<br />

(seconds)<br />

ups.test.interval Interval between self tests (seconds) 1209600 (two weeks)<br />

ups.test.result Results of last self test (opaque string) Bad battery pack<br />

ups.test.date Date of last self test (opaque string) 07/17/12<br />

ups.display.language Language to use on front panel (* E<br />

opaque)<br />

ups.contacts <strong>UPS</strong> external contact sensors (* F0<br />

opaque)<br />

ups.efficiency<br />

Efficiency of the <strong>UPS</strong> (ratio of the 95<br />

output current on the input current)<br />

(percent)<br />

ups.power<br />

Current value of apparent power 500<br />

(Volt-Amps)<br />

ups.power.nominal<br />

Nominal value of apparent power 500<br />

(Volt-Amps)<br />

ups.realpower Current value of real power (Watts) 300<br />

ups.realpower.nominal Nominal value of real power (Watts) 300<br />

ups.beeper.status<br />

<strong>UPS</strong> beeper status (enabled, disabled enabled<br />

or muted)<br />

ups.type <strong>UPS</strong> type (* opaque) offline<br />

ups.watchdog.status<br />

<strong>UPS</strong> watchdog status (enabled or disabled<br />

disabled)<br />

ups.start.auto <strong>UPS</strong> starts when mains is (re)applied yes<br />

ups.start.battery Allow to start <strong>UPS</strong> from battery yes<br />

ups.start.reboot<br />

<strong>UPS</strong> coldstarts from battery (enabled yes<br />

or disabled)<br />

ups.shutdown<br />

Enable or disable <strong>UPS</strong> shutdown<br />

ability (poweroff)<br />

enabled<br />

Note<br />

When present, the value of ups.start.auto has an impact on shutdown.* commands. For the sake of coherence, shutdown<br />

commands will set ups.start.auto to the right value before issuing the command. That is, shutdown.stayoff will first set<br />

ups.start.auto to no, while shutdown.return will set it to yes.<br />

C.1.3<br />

input: Incoming line/power information<br />

Name Description Example value<br />

input.voltage Input voltage 121.5<br />

input.voltage.maximum Maximum incoming voltage seen 130<br />

input.voltage.minimum Minimum incoming voltage seen 100<br />

input.voltage.nominal Nominal input voltage 120<br />

input.voltage.extended Extended input voltage range no<br />

input.transfer.delay<br />

Delay before transfer to mains 60<br />

(seconds)<br />

input.transfer.reason Reason for last transfer to battery (* T<br />

opaque)<br />

input.transfer.low Low voltage transfer point 91<br />

input.transfer.high High voltage transfer point 132<br />

input.transfer.low.min<br />

smallest settable low voltage transfer<br />

point<br />

85