Automation stations - Compact series<br />

The mounting technique and the fixed configuration of integrated I/Os in the<br />

compact series <strong>automation</strong> stations make them ideal for control of small and<br />

distributed plant. The I/Os in these <strong>automation</strong> stations can be adapted to various<br />

types of signal.<br />

The <strong>automation</strong> stations are installed in the control panel. The operator units are<br />

connected to BACnet, PPS bus or HMI connection.<br />

Automation station PXC22-E.D<br />

Plant size I/O: 12 22 36 36 52 10<br />

UI 4 12 18 12 16 4<br />

DI 2 0 4 12 16 4<br />

AO 4 4 6 6 8 0<br />

DO 2 6 8 6 12 2<br />

BACnet/LonTalk PXC12.D PXC22.D PXC236.D PXC36-S PXC52<br />

BACnet/LonTalk<br />

modem<br />

connection<br />

PXC12-T.D PXC22-T.D PXC36-T.D PXC10-TL<br />

BACnet/IP PXC12-E.D PXC22-E.D PXC36-E.D<br />

Input and output options<br />

UI<br />

DI<br />

AO<br />

DO<br />

Universal inputs, which can be connected to passive (LG-Ni 1000) and active<br />

(DC 0…10 V) sensor elements, or to binary volt-free contacts, for signaling<br />

functions.<br />

For PXC…D, a meter at 20 Hz available as an option.<br />

Binary inputs for signaling functions.<br />

For PXC10TL, PXC36-S and PXC52, meter functions also available as an option<br />

(max. 4 meters per PXC… at 20 Hz).<br />

Analog outputs for the connection of 0 ... 10 V actuators or for binary control. Via<br />

the program structure, analog outputs can also be programmed as binary switch<br />

functions and connected to 24 V/20 mA loads.<br />

AC 230 V / 2A relay outputs for binary control.<br />

Up to 5 QAX3… room units can be connected to all compact series <strong>automation</strong><br />

stations.<br />

The PXC36-S <strong>automation</strong> station also incorporates a manual switch and further<br />

LED indicators. The manual controls, with switch positions "Auto/Stop/Manual" or<br />

"Auto/0/1/2", can be used for direct switch control of actuators or freely configured<br />

in software for other purposes.<br />

Further, the PXC10-TL <strong>automation</strong> station is optimized for wall mounting and has a<br />

built-in 230 V supply, and a freely-programmable LED button.<br />

The PXC…-T.D <strong>automation</strong> stations for direct modem connection allow for remote<br />

management and alarming using <strong>DESIGO</strong> INSIGHT.<br />

30 / 64<br />

Siemens <strong>DESIGO</strong> Building <strong>automation</strong> and control <strong>system</strong> CM110660en_03<br />

Building Technologies<br />

System description