Commissioning<br />

For integration operation the corresponding firmware must be loaded into the PXC...-U<br />

automation station.<br />

Disposal<br />

The device includes electrical and electronic components and must not be disposed of<br />

as domestic waste.<br />

Current local legislation must be observed.<br />

Technical data<br />

Elements of the user interface Service pin<br />

Programming mode<br />

<strong>KNX</strong> / <strong>EIB</strong> interface<br />

Stranded or solid conductors,<br />

2 x 1.0 mm 2<br />

<strong>KNX</strong> / <strong>EIB</strong> bus Interface type <strong>KNX</strong> / <strong>EIB</strong> (electrically isolated)<br />

Transceiver<br />

TP-UART<br />

Bus current<br />

5 mA<br />

Baud rate<br />

9.6 kbit/s<br />

Bus topology, bus termination<br />

Refer to <strong>KNX</strong> / <strong>EIB</strong> manual<br />

Service interface<br />

RJ45<br />

Housing<br />

Protection standard to EN 60529 IP 30<br />

protection standard<br />

Protection class Insulation protection class II<br />

Ambient conditions Normal operation Class 3K5 to IEC 721<br />

Temperature 0 ... 50 °C<br />

Humidity<br />

< 85 % rh<br />

Transport Class 2K3 to IEC 721<br />

Temperature – 25 ... 65 °C<br />

Humidity<br />

< 95 % rh<br />

Industry standards<br />

Product safety<br />

Automatic electronic controls <strong>for</strong><br />

household and similar use EN 60730-1<br />

Special requirements <strong>for</strong> energy controllers EN 60730-2-11<br />

Electromagnetic compatibility<br />

Interference immunity<br />

EN 61000-6-2 (Industry)<br />

Emitted interference<br />

EN 61000-6-3 (Residential)<br />

Meets the requirements <strong>for</strong> CE marking:<br />

EMC Directive<br />

2004/108/EG<br />

Dimensions<br />

See “Dimensions”<br />

Weight Excluding packaging 75 g<br />

With packaging<br />

95 g<br />

<strong>Siemens</strong> <strong>PXA30</strong>-<strong>K11</strong> – <strong>Extension</strong> <strong>module</strong> <strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong> CM1N9280en_02<br />

Building Technologies 18 May 2009<br />

3/4