STUDENT HANDOUT<br />

DEMYSTIFYING HAZMAT CHEMISTRY<br />

Flammability<br />

When plotting the flammability risk on a hazard ladder, we generally look at the concentration of<br />

a gas or vapor in air, just as we do when plotting toxicity. The most important value is the Lower<br />

Explosive Limit (LEL). Below the LEL, vapors are too lean to burn. At the other end of the scale is<br />

the Upper Explosive Limit (UEL). Above this concentration, vapors are too rich to burn. However,<br />

from the LEL to the UEL, ignition is possible. This is known as the flammable range.<br />

Flammable Range<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Only atmospheres that are well below the LEL are safe to enter. Many agencies have SOPs that<br />

prohibit working in an atmosphere greater than 10% of the LEL. (That’s 10% of the LEL, not a<br />

10% contaminant concentration in the atmosphere.) In part, this comes from OSHA regulations<br />

that prohibit working in confined spaces with more than 10% of the LEL. However, when the environment<br />

does not meet the definition of a confined space, the Environmental Protection Agency’s<br />

guidelines suggest that hazardous materials technicians can keep working up to 25% of the LEL<br />

if they’re cautious and use continuous monitoring. Both limits (10% and 25%) still leave a good<br />

margin for error to guard against everything from fluctuations in the chemical concentration to<br />

defective monitors or errors in interpreting the meter readings.<br />

Although the vapors are too rich to burn above the UEL, you should not consider that to be a safe<br />

atmosphere since the vapor concentration may drop to within the flammable range during your<br />

emergency response operations.<br />

You can plot flammable range on a hazard ladder also. This gives you a clear visual representation<br />

of the flammability risk. The wider the flammable range, the greater the risk. Conversely,<br />

products with a narrow flammable range present less of a risk.<br />

Plotting LEL and UEL<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Continuing Challenge 2007 Page 13 © 2007 Firebelle Productions and CHES