SIMATIC S7-<strong>300</strong><br />
Function modules<br />
FM 350-2 counter module<br />
■ Overview<br />
• For direct connection of 24 V incremental encoders, directional<br />
elements, initiators or NAMUR sensors<br />
• Compare function with programmable comparison values<br />
(number depends on operating mode).<br />
• Integrated digital outputs to output the response upon<br />
reaching the comparison value.<br />
• Operating modes:<br />
- Continuous/one-shot/periodic counting<br />
- Frequency/speed control<br />
- Period measurement<br />
-Proportioning<br />
4<br />
Note:<br />
SIMODRIVE Sensor/Motion Connect 500 feature incremental<br />
encoders and preassembled connecting cables for counting<br />
and positioning functions.<br />
Additional information is available in the Inter<strong>net</strong> under:<br />
• 8-channel intelligent counter mo dule for universal counter and<br />
measurement tasks<br />
http://www.siemens.com/<strong>simatic</strong>-technology<br />
■ Technical specifications<br />
6ES7 350-2AH00-0AE0<br />
Voltages and currents<br />
Auxiliary voltage 1L+, load voltage<br />
2 L+<br />
- Rated value (DC) 24 V<br />
- permissible range, lower limit 20.4 V<br />
(DC)<br />
- permissible range, upper limit 28.8 V<br />
(DC)<br />
Current consumption<br />
• from load voltage L+ (no load), 150 mA<br />
max.<br />
• from backplane bus 5 V DC, max. 100 mA<br />
• Power dissipation, typical 10 W<br />
Connection system<br />
• Requisite front connector<br />
1 x 40-pin<br />
Digital inputs<br />
• Number of digital inputs 8<br />
• Functions<br />
1 each for gate start / gate stop<br />
Length of cable<br />
- Length of cable shielded, max 100 m<br />
Input voltage<br />
- for signal "0" -3 to 5 V<br />
- for signal "1" 11 to 30.2 V<br />
Input current<br />
- for 0 signal, max.(permissible 2 mA<br />
closed-circuit current)<br />
- for 1 signal, typical 9 mA<br />
Input delay (at rated value of the<br />
input voltage)<br />
• For standard inputs<br />
- at 0 to 1, max. 50 µs<br />
6ES7 350-2AH00-0AE0<br />
Digital outputs<br />
• Number of digital outputs 8<br />
• Length of cable shielded, max. 600 m<br />
• Length of cable unshielded, max. 100 m<br />
• Short-circuit protection of the Yes<br />
output<br />
• Limitation of voltage induced on L+ (-40 V)<br />
circuit interruption to<br />
Output voltage<br />
- for 1 signal L+ (-0.8 V)<br />
Output current<br />
- for 1 signal rated value 0.5 A<br />
- for 0 signal residual current, max. 0.5 mA<br />
Output delay at resistive load<br />
- "0" to "1", max. <strong>300</strong> µs<br />
Switching frequency<br />
- at resistive load, max. 500 Hz<br />
- at inductive load, max. 0.5 Hz<br />
Summation current of the outputs<br />
(per group)<br />
- vertical installation,<br />
2 A<br />
up to 40 °C, max.<br />
- horizontal installation,<br />
4 A<br />
up to 40 °C, max.<br />
- horizontal installation,<br />
2 A<br />
up to 60 °C, max.<br />
Sensor supply<br />
• Output voltage<br />
NAMUR sensor supply:<br />
8.2 V +/-2%<br />
• Output current, rated value 200 mA<br />
• Short-circuit protection<br />
Yes<br />
Siemens ST 70 · 2005<br />
4/95