09.09.2015 Views

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SIMATIC S7-<strong>300</strong><br />

Function modules<br />

FM 350-2 counter module<br />

■ Overview<br />

• For direct connection of 24 V incremental encoders, directional<br />

elements, initiators or NAMUR sensors<br />

• Compare function with programmable comparison values<br />

(number depends on operating mode).<br />

• Integrated digital outputs to output the response upon<br />

reaching the comparison value.<br />

• Operating modes:<br />

- Continuous/one-shot/periodic counting<br />

- Frequency/speed control<br />

- Period measurement<br />

-Proportioning<br />

4<br />

Note:<br />

SIMODRIVE Sensor/Motion Connect 500 feature incremental<br />

encoders and preassembled connecting cables for counting<br />

and positioning functions.<br />

Additional information is available in the Inter<strong>net</strong> under:<br />

• 8-channel intelligent counter mo dule for universal counter and<br />

measurement tasks<br />

http://www.siemens.com/<strong>simatic</strong>-technology<br />

■ Technical specifications<br />

6ES7 350-2AH00-0AE0<br />

Voltages and currents<br />

Auxiliary voltage 1L+, load voltage<br />

2 L+<br />

- Rated value (DC) 24 V<br />

- permissible range, lower limit 20.4 V<br />

(DC)<br />

- permissible range, upper limit 28.8 V<br />

(DC)<br />

Current consumption<br />

• from load voltage L+ (no load), 150 mA<br />

max.<br />

• from backplane bus 5 V DC, max. 100 mA<br />

• Power dissipation, typical 10 W<br />

Connection system<br />

• Requisite front connector<br />

1 x 40-pin<br />

Digital inputs<br />

• Number of digital inputs 8<br />

• Functions<br />

1 each for gate start / gate stop<br />

Length of cable<br />

- Length of cable shielded, max 100 m<br />

Input voltage<br />

- for signal "0" -3 to 5 V<br />

- for signal "1" 11 to 30.2 V<br />

Input current<br />

- for 0 signal, max.(permissible 2 mA<br />

closed-circuit current)<br />

- for 1 signal, typical 9 mA<br />

Input delay (at rated value of the<br />

input voltage)<br />

• For standard inputs<br />

- at 0 to 1, max. 50 µs<br />

6ES7 350-2AH00-0AE0<br />

Digital outputs<br />

• Number of digital outputs 8<br />

• Length of cable shielded, max. 600 m<br />

• Length of cable unshielded, max. 100 m<br />

• Short-circuit protection of the Yes<br />

output<br />

• Limitation of voltage induced on L+ (-40 V)<br />

circuit interruption to<br />

Output voltage<br />

- for 1 signal L+ (-0.8 V)<br />

Output current<br />

- for 1 signal rated value 0.5 A<br />

- for 0 signal residual current, max. 0.5 mA<br />

Output delay at resistive load<br />

- "0" to "1", max. <strong>300</strong> µs<br />

Switching frequency<br />

- at resistive load, max. 500 Hz<br />

- at inductive load, max. 0.5 Hz<br />

Summation current of the outputs<br />

(per group)<br />

- vertical installation,<br />

2 A<br />

up to 40 °C, max.<br />

- horizontal installation,<br />

4 A<br />

up to 40 °C, max.<br />

- horizontal installation,<br />

2 A<br />

up to 60 °C, max.<br />

Sensor supply<br />

• Output voltage<br />

NAMUR sensor supply:<br />

8.2 V +/-2%<br />

• Output current, rated value 200 mA<br />

• Short-circuit protection<br />

Yes<br />

Siemens ST 70 · 2005<br />

4/95