■ Technical specifications (continued)<br />

6ES7 332-5RD00-0AB0<br />

Voltages and currents<br />

Load voltage L+<br />

- Rated value (DC) 24 V<br />

Current consumption<br />

• from load voltage L+ (no load), 180 mA<br />

max.<br />

• from backplane bus 5 V DC, max. 80 mA<br />

• Power dissipation, typical 4 W<br />

Connection system<br />

• Requisite front connector<br />

20-pin<br />

Analog outputs<br />

• Number of analog outputs 4<br />

• Length of cable shielded, max 200 m<br />

• Voltage output, short-circuit Yes<br />

protection<br />

• Voltage output, short-circuit 70 mA<br />

current, max<br />

• Current output, open-circuit 14 V<br />

voltage, max.<br />

Output ranges, current<br />

- 0 to 20 mA Yes<br />

- 4 to 20 mA Yes<br />

Actuator connection<br />

- for current output 2-wire Yes<br />

connection<br />

Burden resistance (in the nominal<br />

output range)<br />

- at current outputs, max. 500 MΩ<br />

Analog value formation<br />

Integration and conversion<br />

time/triggering per channel<br />

- with over-range (bits incl. sign), 15 Bit<br />

max.<br />

- Basic conversion time, ms 2.5 ms<br />

Ex(i)-modules<br />

Maximum values of the output<br />

circuits (per channel)<br />

- Ca (permissible external 850 nF<br />

capacity), max.<br />

- Io (short-circuit current), max. 70 mA<br />

- La (permissible external 6.6 mH<br />

inductance), max.<br />

- Po (load power), max. 440 mW<br />

- Uo (output opencircuit<br />

voltage),<br />

14 V<br />

max.<br />

SIMATIC S7-<strong>300</strong><br />

Ex input / output modules<br />

Ex analog I/O modules<br />

6ES7 332-5RD00-0AB0<br />

Error/accuracies<br />

Operational limit in the entire temperature<br />

range<br />

- Relative to the output range, +/- 0.55 %<br />

current<br />

Basic error limit (operational limit<br />

at 25 °C)<br />

- relative to the output range, +/- 0.2 %<br />

current<br />

Status information/ interrupts/<br />

diagnostics<br />

Diagnostics<br />

- Diagnostic information can be Yes<br />

read out<br />

- Range overflow Yes<br />

- Wire break in actuator cable Yes<br />

- Group error Yes<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- Electrical isolation,<br />

Yes<br />

analog output functions<br />

Permissible potential difference<br />

• between the outputs and MANA 60 V DC/ 30 V AC<br />

(UCM)<br />

• between the outputs (UCM) 60 V DC/ 30 V AC<br />

Standards, approvals,<br />

certification<br />

• Type of protection to comply [EEx ib] IIC<br />

with EN 50020 (CENELEC)<br />

• Type of protection to comply CL.I, DIV 2, GP A,B,C,D T4<br />

with FM<br />

• PTB test number<br />

Ex-96.D.2026X<br />

Dimensions and weight<br />

• Weight, approx.<br />

280 g<br />

4<br />