09.09.2015 Views

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

SIMATIC S7-<strong>300</strong><br />

Ex input / output modules<br />

Ex analog I/O modules<br />

4<br />

■ Technical specifications (continued)<br />

6ES7 331-<br />

7RD00-0AB0<br />

6ES7 331-<br />

7SF00-0AB0<br />

Sensor<br />

Sensing element connection<br />

- for current measurement, Yes<br />

Yes<br />

as 2-wire measuring transducer<br />

- for current measurement, Yes<br />

Yes<br />

as 4-wire measuring transducer<br />

Ex(i)-modules<br />

Maximum values of the input<br />

circuits (per channel)<br />

- Ca (permissible external 90 nF 60 µF<br />

capacity), max.<br />

- Io (short-circuit current), max. 68.5 mA 28.8 mA<br />

- La (permissible external inductance),<br />

7.5 mH 40 mH<br />

max.<br />

- Po (load power), max. 431 mW 41.4 mW<br />

- Ri, max 50 Ω<br />

- Uo (output open-circuit voltage), 25.2 V 5.9 V<br />

max.<br />

Error/accuracies<br />

• Temperature error<br />

(relative to the input range)<br />

Operational limit in the entire<br />

temperature range<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance thermometer<br />

Basic error limit (operational limit at<br />

25 °C)<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance thermometer<br />

Interference voltage suppression for<br />

f = n x (fl +/- 1 %)<br />

- Series-mode interference<br />

(peak value of interference <<br />

rated value input range<br />

- Common-mode interference,<br />

min<br />

+/- 0.45 %<br />

+/- 0.1 %<br />

Temperature<br />

error: 0.001 to<br />

0.002 %/K<br />

0.09 to 0.04 %<br />

+/- 0.1 %<br />

60 dB 60 dB<br />

130 dB 130 dB<br />

6ES7 331-<br />

7RD00-0AB0<br />

6ES7 331-<br />

7SF00-0AB0<br />

Status information/<br />

interrupts/ diagnostics<br />

Diagnostics<br />

- Diagnostic information can be Yes<br />

Yes<br />

read out<br />

- Range overflow Yes Yes<br />

- Wire break in sensor cable Yes Yes<br />

- Short circuit in sensor cable Yes Yes<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- Electrical isolation,<br />

Yes<br />

Yes<br />

analog inputs<br />

Permissible potential difference<br />

• between the inputs (UCM) 60 V DC 60 V DC<br />

• between the in puts and MANA 60 V DC 30 V DC<br />

(UCM)<br />

Standards, approvals,<br />

certification<br />

• Type of protection to comply with<br />

EN 50020 (CENELEC)<br />

[EEx ib] IIC [EEx ib] IIC<br />

• Type of protection to comply with<br />

FM<br />

CL.I, DIV 2,<br />

GP A,B,C,D T4<br />

CL.I, DIV 2,<br />

GP A,B,C,D T4<br />

• PTB test number Ex-96.D.2092X Ex-96.D.2108X<br />

Dimensions and weight<br />

• Weight, approx. 290 g 210 g<br />