simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
■ Overview<br />
SIMATIC S7-<strong>300</strong><br />
Ex input / output modules<br />
Ex analog I/O modules<br />
• I/O modules for applications within potentially explosive<br />
chemical plants<br />
• For connecting sensors and ac tuators from zones 1 and 2 in<br />
hazardous area installations<br />
• Associated electrical equipmen t [EEx ib] IIC in accordance<br />
with DIN 50020<br />
• For isolation of non-IS circuits of the automation system and<br />
the IS circuits from the process<br />
4<br />
■ Technical specifications<br />
6ES7 331-<br />
7RD00-0AB0<br />
6ES7 331-<br />
7SF00-0AB0<br />
Voltages and currents<br />
Load voltage L+<br />
- Rated value (DC) 24 V 24 V<br />
Power supply of measuring<br />
transducers<br />
- Available Yes<br />
- Rated value (DC) 13 V; at 22 mA<br />
- Open-circuit voltage (DC) 25.2 V<br />
Current consumption<br />
• from backplane bus 5 V DC, max. 60 mA 120 mA<br />
• from supply voltage L+, max. 150 mA<br />
• Power dissipation, typical 3 W 0.6 W<br />
Connection system<br />
• Requisite front connector 20-pin 20-pin<br />
Analog inputs<br />
• Number of analog inputs 4 8; 8 x thermocouples,<br />
4 x RTD thermistors<br />
• Length of cable shielded, max 200 m 200 m;<br />
HTC: 50 m<br />
• Permissible input voltage for the 40 mA<br />
current input (destruction limit),<br />
max.<br />
Input ranges (rated values),<br />
currents<br />
- 0 to 20 mA Yes<br />
- 4 to 20 mA Yes<br />
6ES7 331-<br />
7RD00-0AB0<br />
6ES7 331-<br />
7SF00-0AB0<br />
Analog inputs (continued)<br />
Input ranges (rated values),<br />
thermocouples<br />
- Type B Yes<br />
- Type E Yes<br />
- Type J Yes<br />
- Type K Yes<br />
- Type L Yes<br />
- Type N Yes<br />
- Type R Yes<br />
- Type S Yes<br />
- Type T Yes<br />
- Type U Yes<br />
Input ranges (rated values),<br />
resistance thermometer<br />
- Ni 100 Yes<br />
- Pt 100 Yes<br />
- Pt 200 Yes<br />
Analog value formation<br />
• Measuring principle SIGMA-DELTA SIGMA-DELTA<br />
Integration and conversion<br />
time/triggering per channel<br />
- with over-range (bits incl. sign),<br />
max.<br />
16 Bit;<br />
10 to 15 bits +<br />
sign<br />
16 Bit;<br />
10 to 15 bits +<br />
sign<br />
Yes;<br />
2.5 to 100 ms<br />
- Integration time parameterizable Yes;<br />
2.5 to 100 ms<br />
- Interference voltage suppression<br />
10 to 400 Hz 10 to 400 Hz<br />
for interference frequency f1<br />
in Hz<br />
Siemens ST 70 · 2005<br />
4/89