SIMATIC S7-<strong>300</strong><br />

Ex input / output modules<br />

Ex digital I/O modules<br />

■ Overview<br />

• I/O modules for applications within potentially explosive<br />

chemical plants<br />

• For connecting sensors and ac tuators from zones 1 and 2 in<br />

hazardous area installations<br />

• Associated electrical equipmen t [EEx ib] IIC in accordance<br />

with DIN 50020<br />

• For isolating non-intrinsically safe circuits of the programmable<br />

logic controller and the intrinsically safe circuits from the<br />

process<br />

■ Technical specifications<br />

6ES7 321-7RD00-0AB0<br />

Voltages and currents<br />

Load voltage L+<br />

- Rated value (DC) 24 V<br />

Current consumption<br />

• from load voltage L+ (no load), 50 mA<br />

max.<br />

• from backplane bus 5 V DC, max. 80 mA<br />

• Power dissipation, typical 1.1 W<br />

Connection system<br />

• Requisite front connector<br />

20-pin<br />

Digital inputs<br />

• Number of NAMUR inputs 4<br />

Length of cable<br />

- Length of cable unshielded, max. 200 m<br />

Input voltage<br />

- Rated value, DC 8.2 V; from internal circuit supply<br />

Input current<br />

- At broken wire, max. 0.1 mA<br />

- At short circuit, max. 8.5 mA<br />

• For NAMUR sensor<br />

- For 0 signal 0.35 to 1.2 mA<br />

- For 1 signal 2.1 to 7 mA<br />

Input delay (at rated value of the<br />

input voltage)<br />

- Input frequency<br />

2 kHz<br />

(at 0.1ms delay time), max.<br />

• for NAMUR inputs<br />

- parameterizable Yes; 0.1 / 0.5 / 3 / 15 / 20 ms<br />

(parametizable, plus 0.25 ms<br />

preparation time)<br />

Sensor supply<br />

• Output voltage<br />

via inputs<br />

6ES7 321-7RD00-0AB0<br />

Sensor<br />

Connectable encoders<br />

- NAMUR sensor Yes; Two-wire connection<br />

Ex(i)-modules<br />

Maximum values of the input<br />

circuits (per channel)<br />

- Ca (permissible external 3 µF<br />

capacity), max.<br />

- Io (short-circuit current), max. 14.1 mA<br />

- La (permissible external inductance),<br />

max.<br />

100 mH<br />

- Po (load power), max. 33.7 mW<br />

- Uo (output open-circuit voltage), 10 V<br />

max.<br />

Status information/ interrupts/<br />

diagnostics<br />

Diagnostics<br />

- Diagnostic information can be Yes<br />

read out<br />

Potentials/ electrical isolation<br />

Digital input functions<br />

- Electrical isolation,<br />

Yes<br />

digital input functions<br />

- between the channels,<br />

1<br />

in groups of<br />

Standards, approvals,<br />

certification<br />

• Type of protection to comply [EEx ib] IIC<br />

with EN 50020 (CENELEC)<br />

• Type of protection to comply CL.2, DIV 2, GP A,B,C,D T4<br />

with FM<br />

• PTB test number<br />

Ex-96.D.2094X<br />

Dimensions and weight<br />

• Weight, approx.<br />

230 g<br />