4<br />
SIMATIC S7-<strong>300</strong><br />
F digital / analog modules<br />
SM 336 F analog input - Safety Integrated<br />
■ Overview<br />
• Analog inputs for the failsafe SIMATIC S7 systems<br />
• For connection of analog sensors with voltage and current<br />
signals<br />
• With integrated safety func tions for failsafe operation<br />
• Can be used in the ET 200M distributed I/O station with<br />
SIMATIC S7-31xF-2 DP, S7-416F-2 and S7-400F/FH<br />
• Suitable for use in standard operation in the same way as<br />
S7-<strong>300</strong> modules<br />
■ Technical specifications<br />
6ES7 336-1HE00-0AB0<br />
Voltages and currents<br />
Load voltage L+<br />
- Rated value (DC) 24 V<br />
- Reverse polarity protection Yes<br />
Current consumption<br />
• from backplane bus 5 V DC, max. 90 mA<br />
• from supply voltage L+, max. 160 mA; typ.<br />
• Power dissipation, typical 4.25 W<br />
Connection system<br />
• Requisite front connector<br />
40-pin<br />
Analog inputs<br />
• Number of analog inputs 6<br />
• Number of analog inputs for 4<br />
voltage measurement<br />
• Length of cable shielded, max 200 m<br />
• Permissible input voltage for the 30 V<br />
voltage input (destruction limit),<br />
max.<br />
• Permissible input voltage for the 40 mA<br />
current input (destruction limit),<br />
max.<br />
Input ranges (rated values),<br />
voltages<br />
- 0 to +10 V Yes<br />
Input ranges (rated values),<br />
currents<br />
- 0 to 20 mA Yes<br />
- 4 to 20 mA Yes<br />
Analog value formation<br />
Integration and conversion<br />
time/triggering per channel<br />
- with over-range (bits incl. sign), 14 Bit<br />
max<br />
- Integration time, ms 20 ms (at 50 Hz);<br />
16.66 ms (at 60 Hz)<br />
- Interference voltage suppression<br />
for interference frequency f1<br />
38 dB<br />
in Hz<br />
Sensor<br />
Sensing element connection<br />
- for current measurement, Yes<br />
as 2-wire measuring transducer<br />
- for current measurement, Yes<br />
as 4-wire measuring transducer<br />
6ES7 336-1HE00-0AB0<br />
Error/accuracies<br />
Operational limit in the entire<br />
temperature range<br />
- relative to the input range, +/- 0.48 %<br />
voltage<br />
- relative to the input range +/- 0.48 %<br />
current<br />
Basic error limit (operational<br />
limit at 25 °C)<br />
- relative to the input range, +/- 0.4 %<br />
voltage<br />
- relative to the input range, +/- 0.4 %<br />
current<br />
Status information/<br />
interrupts/ diagnostics<br />
Alarme<br />
- Diagnostic interrupt Yes; parameterizable<br />
Diagnostics<br />
- Diagnostic information can be Yes<br />
read out<br />
Insulation<br />
• Insulation tested with<br />
500 V DC/ 350 V AC<br />
Potentials/ electrical isolation<br />
Analog output functions<br />
- between the channels No<br />
- between the channels and the Yes<br />
backplane bus<br />
- between the channels and the<br />
electronics power supply<br />
Standards, approvals,<br />
certification<br />
Maximum safety level that can be<br />
achieved in safety mode<br />
- to comply with DIN V 19250 AK 6<br />
- to comply with EN 954 Cat. 4<br />
- to comply with IEC 61508 SIL 3<br />
Dimensions and weight<br />
• Weight, approx.<br />
480 g<br />
• Width<br />
80 mm<br />
• Height<br />
125 mm<br />
•Depth<br />
120 mm<br />
Yes; only when external sensor<br />
power supply<br />
4/82 Siemens ST 70 · 2005