4<br />

SIMATIC S7-<strong>300</strong><br />

F digital / analog modules<br />

SM 336 F analog input - Safety Integrated<br />

■ Overview<br />

• Analog inputs for the failsafe SIMATIC S7 systems<br />

• For connection of analog sensors with voltage and current<br />

signals<br />

• With integrated safety func tions for failsafe operation<br />

• Can be used in the ET 200M distributed I/O station with<br />

SIMATIC S7-31xF-2 DP, S7-416F-2 and S7-400F/FH<br />

• Suitable for use in standard operation in the same way as<br />

S7-<strong>300</strong> modules<br />

■ Technical specifications<br />

6ES7 336-1HE00-0AB0<br />

Voltages and currents<br />

Load voltage L+<br />

- Rated value (DC) 24 V<br />

- Reverse polarity protection Yes<br />

Current consumption<br />

• from backplane bus 5 V DC, max. 90 mA<br />

• from supply voltage L+, max. 160 mA; typ.<br />

• Power dissipation, typical 4.25 W<br />

Connection system<br />

• Requisite front connector<br />

40-pin<br />

Analog inputs<br />

• Number of analog inputs 6<br />

• Number of analog inputs for 4<br />

voltage measurement<br />

• Length of cable shielded, max 200 m<br />

• Permissible input voltage for the 30 V<br />

voltage input (destruction limit),<br />

max.<br />

• Permissible input voltage for the 40 mA<br />

current input (destruction limit),<br />

max.<br />

Input ranges (rated values),<br />

voltages<br />

- 0 to +10 V Yes<br />

Input ranges (rated values),<br />

currents<br />

- 0 to 20 mA Yes<br />

- 4 to 20 mA Yes<br />

Analog value formation<br />

Integration and conversion<br />

time/triggering per channel<br />

- with over-range (bits incl. sign), 14 Bit<br />

max<br />

- Integration time, ms 20 ms (at 50 Hz);<br />

16.66 ms (at 60 Hz)<br />

- Interference voltage suppression<br />

for interference frequency f1<br />

38 dB<br />

in Hz<br />

Sensor<br />

Sensing element connection<br />

- for current measurement, Yes<br />

as 2-wire measuring transducer<br />

- for current measurement, Yes<br />

as 4-wire measuring transducer<br />

6ES7 336-1HE00-0AB0<br />

Error/accuracies<br />

Operational limit in the entire<br />

temperature range<br />

- relative to the input range, +/- 0.48 %<br />

voltage<br />

- relative to the input range +/- 0.48 %<br />

current<br />

Basic error limit (operational<br />

limit at 25 °C)<br />

- relative to the input range, +/- 0.4 %<br />

voltage<br />

- relative to the input range, +/- 0.4 %<br />

current<br />

Status information/<br />

interrupts/ diagnostics<br />

Alarme<br />

- Diagnostic interrupt Yes; parameterizable<br />

Diagnostics<br />

- Diagnostic information can be Yes<br />

read out<br />

Insulation<br />

• Insulation tested with<br />

500 V DC/ 350 V AC<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- between the channels No<br />

- between the channels and the Yes<br />

backplane bus<br />

- between the channels and the<br />

electronics power supply<br />

Standards, approvals,<br />

certification<br />

Maximum safety level that can be<br />

achieved in safety mode<br />

- to comply with DIN V 19250 AK 6<br />

- to comply with EN 954 Cat. 4<br />

- to comply with IEC 61508 SIL 3<br />

Dimensions and weight<br />

• Weight, approx.<br />

480 g<br />

• Width<br />

80 mm<br />

• Height<br />

125 mm<br />

•Depth<br />

120 mm<br />

Yes; only when external sensor<br />

power supply<br />

4/82 Siemens ST 70 · 2005