■ Overview<br />
SIMATIC S7-<strong>300</strong><br />
F digital / analog modules<br />
SM 326 F digital input - Safety Integrated<br />
• Digital inputs for the failsafe SIMATIC S7 systems<br />
• They are suitable for connecting:<br />
- Switches and two-wire proximity switches (BERO)<br />
- Sensors according to NAMUR and connected mechanical<br />
contacts, also for signals from hazardous areas<br />
• With integrated safety func tions for failsafe operation<br />
• Can be used in failsafe mode<br />
- Centrally: with S7-31xF-2DP<br />
(applies only to 6ES7 326-1BK00-0AB0)<br />
- Distributed in ET 200M: with SIMATIC S7-31xF-2DP,<br />
S7-416F-2 and S7-400F/FH<br />
• Suitable for use in standard operation in the same way as<br />
S7-<strong>300</strong> modules<br />
4<br />
■ Technical specifications<br />
6ES7 326-<br />
1RF00-0AB0<br />
6ES7 326-<br />
1BK00-0AB0<br />
Supply voltages<br />
Supply voltage of electronic and<br />
sensor components 1L+/2L+<br />
- Rated value (DC) 24 V 24 V<br />
Current consumption<br />
• from load voltage L+ (no load), 160 mA 450 mA<br />
max.<br />
• from backplane bus 5 V DC, max. 90 mA 100 mA<br />
• Power dissipation, typical 4.5 W 10 W<br />
Connection system<br />
• Requisite front connector 40-pin 40-pin<br />
Digital inputs<br />
• Number of digital inputs 8;<br />
8 (single-channel);<br />
4 (dual-channel)<br />
24<br />
Number of inputs that can be driven<br />
in parallel<br />
- Number of inputs that can be<br />
driven in parallel, up to 40 °C<br />
- Number of inputs that can be<br />
driven in parallel, up to 60 °C<br />
8; vertical<br />
installation<br />
8; horizontal<br />
installation<br />
24<br />
24; (at 24 V)<br />
or 18<br />
(at 28.8 V)<br />
Length of cable<br />
- Length of cable shielded, max. 200 m 200 m<br />
- Length of cable unshielded, max. 100 m 100 m<br />
Input voltage<br />
- Rated value, DC to DIN 19234 24 V<br />
and NAMUR<br />
- for signal "0" -30 to 5 V<br />
- for signal "1" 11 to 30 V<br />
Input current<br />
- for 0 signal, max (permissible 0.35 to 1.2 mA 2 mA<br />
closed-circuit current)<br />
- for 1 signal, typical 2.1 to bis 7 mA 10 mA<br />
6ES7 326-<br />
1RF00-0AB0<br />
6ES7 326-<br />
1BK00-0AB0<br />
Digital inputs (continued)<br />
Input delay (at rated value of the<br />
input voltage)<br />
• For standard inputs<br />
- at 0 to 1, max. 3.4 ms<br />
- at 1 to 0, max. 3.4 ms<br />
• for NAMUR inputs<br />
- at 0 to 1, max 1.2 to 3 ms<br />
- at 1 to 0, max 1.2 to 3 ms<br />
Sensor supply<br />
• Number of outputs 8 4; electrically<br />
isolated<br />
• Output voltage<br />
8.2 V DC<br />
• Output current, rated value<br />
400 mA<br />
Sensor<br />
Connectable encoders<br />
- 2-wire BEROS Yes; when<br />
short-circuit<br />
test deactivated<br />
- permissible closed-circuit<br />
2 mA<br />
current (2-wire BEROS), max.<br />
Ex(i)-modules<br />
• Module for Ex(i) protection Yes<br />
Maximum values of the input<br />
circuits (per channel)<br />
- Ca (permissible external 3 µF<br />
capacity), max.<br />
- Io (short-circuit current), max. 13.9 mA<br />
- La (permissible external inductance),<br />
max.<br />
80 mH<br />
- Po (load power), max. 33.1 mW<br />
- Uo (output open-circuit voltage), 10 V<br />
max.<br />
- Um (fault voltage), max 60 V DC/ 30 V AC<br />
- permissible ambient temperature<br />
Ta, max<br />
60 °C 60 °C<br />
Siemens ST 70 · 2005<br />
4/77