SIMATIC S7-<strong>300</strong><br />

Analog modules<br />

SM 331 analog input modules<br />

4<br />

■ Technical specifications (continued)<br />

Sensor<br />

Sensing element connection<br />

- for current measurement,<br />

as 2-wire measuring transducer<br />

- for current measurement,<br />

as 4-wire measuring transducer<br />

- for resistance measurement,<br />

with 2-wire connection<br />

- for resistance measurement,<br />

with 3-wire connection<br />

- for resistance measurement,<br />

with 4-wire connection<br />

Error/accuracies<br />

Operational limit in the entire<br />

temperature range<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Basic error limit<br />

(operational limit at 25 °C)<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Status information/<br />

interrupts/ diagnostics<br />

Interrupts<br />

6ES7 331-7PF00-0AB0 6ES7 331-7PF10-0AB0 6ES7 331-7NF00-0AB0 6ES7 331-7NF10-0AB0<br />

Yes; without resistance<br />

correction<br />

Yes<br />

Yes<br />

+/- 0.1 %<br />

+/- 1 K<br />

+/- 0.05 %<br />

+/- 0.5 K<br />

- Diagnostic interrupt Yes; parameterizable<br />

per group<br />

Yes; with external<br />

measuring transducer;<br />

possible with separate<br />

power supply for the<br />

measuring transducer<br />

Yes<br />

+/- 1 K +/- 0.1 %; +/-0.7% +/- 0.1 %<br />

+/- 0.3 %; +/-0.9% +/- 0.1 %<br />

+/- 0.5 K +/- 0.05 % +/- 0.05 %<br />

Yes; parameterizable<br />

per group<br />

+/- 0.05 % +/- 0.05 %<br />

Yes; parameterizable<br />

- Limit value interrupt Yes; parameterizable Yes; parameterizable Yes; parameterizable<br />

channels 0 and 2<br />

Diagnostics<br />

- Diagnostic information can be Yes Yes Yes Yes<br />

read out<br />

Insulation<br />

• Insulation tested with 500 V DC 500 V DC 500 V DC 500 V AC<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- between the channels Yes Yes Yes<br />

- between the channels,<br />

2 2 2<br />

in groups of<br />

- between the channels and Yes Yes Yes Yes<br />

the backplane bus<br />

Dimensions and weight<br />

• Weight, approx. 272 g 272 g 272 g 272 g<br />

• Width 40 mm 40 mm 40 mm 40 mm<br />

• Height 125 mm 125 mm 125 mm 125 mm<br />

•Depth 120 mm 120 mm 120 mm 120 mm<br />

Yes; with external measuring<br />

transducer, power<br />

supply; possible with<br />

separate power supply<br />

for the measuring transducer<br />

Yes<br />

Yes; parameterizable<br />

Yes; parameterizable all<br />

channels (end-of-cycle<br />

interrupt also supported<br />

throughout modules)<br />

4/64 Siemens ST 70 · 2005