SIMATIC S7-<strong>300</strong><br />
Analog modules<br />
SM 331 analog input modules<br />
■ Technical specifications (continued)<br />
Sensor<br />
6ES7 331-7KF02-0AB0 6ES7 331-7HF01-0AB0 6ES7 331-1KF01-0AB0 6ES7 331-7KB02-0AB0<br />
Sensing element connection<br />
- for current measurement,<br />
as 2-wire measuring transducer<br />
- for current measurement,<br />
as 4-wire measuring transducer<br />
- for resistance measurement,<br />
with 2-wire connection<br />
- for resistance measurement,<br />
with 3-wire connection<br />
- for resistance measurement,<br />
with 4-wire connection<br />
Error/accuracies<br />
Operational limit in the entire<br />
temperature range<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
- relative to the input range,<br />
resistance<br />
- relative to the input range,<br />
resistance thermometer<br />
Basic error limit<br />
(operational limit at 25 °C)<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
- relative to the input range,<br />
resistance<br />
- relative to the input range,<br />
resistance thermometer<br />
Yes Yes Yes; with extreme power Yes<br />
supply<br />
Yes Yes Yes Yes<br />
Yes Yes Yes<br />
Yes Yes Yes<br />
Yes Yes Yes<br />
+/- 1 %; +/-1% (80 mV),<br />
+/-0.6% (250-1000 mV),<br />
+/-0.8% (2.5-10 mV)<br />
+/- 0.7 %;<br />
from 3.2 - 20mA<br />
+/- 0.7 %;<br />
50, <strong>300</strong>, 600 ohms<br />
+/- 0.7 %;<br />
+/-0.7% (Pt100/ Ni100)<br />
+/-0.8% (Pt100 climat)<br />
+/- 0.6 %;<br />
+/-0.4% (250-1000mV)<br />
+/-0.6% (2.5-10mV)<br />
+/-0.7% (80mV)<br />
+/- 0.4 % +/- 0.6 %;<br />
+/-0.6%<br />
(+/-5V,10V,1-5V,0-10V;<br />
+/-0.5%<br />
(+/-50mV,500mV,1V<br />
+/- 0.3 % +/- 0.5 %;<br />
+/-20mA,0-20mA,4-20mA<br />
+/- 0.5 %; 0-6kOhms,<br />
0-600kOhms<br />
1 Kelvin<br />
(Pt100,Ni100,climatic;<br />
Ni1000,LG-Ni1000,standard;<br />
Ni1000,LG-<br />
Ni1000,climatic); 1.2<br />
Kelvin (Pt100,Ni100,<br />
standard)<br />
+/- 0.25 % +/- 0.4 %;<br />
0.4%<br />
(+/-5V,10V,1-5V,0-10V);<br />
0.3% (+/ 50mV,500mV,1V)<br />
+/- 0.5 %; 3.2-20 mA +/- 0.2 % +/- 0.3 %;<br />
+/-20mA, 0-20mA, 4-20mA<br />
+/- 0.5 %;<br />
150, <strong>300</strong>, 600 ohms<br />
+/- 0.6 %;<br />
+/-0.5% (Pt100/ Ni100)<br />
+/-0.6% (Pt100 climatic)<br />
Status information/ interrupts/<br />
diagnostics<br />
Interrupts<br />
- Diagnostic interrupt Yes; parameterizable<br />
channels 0 and 2<br />
- Limit value interrupt Yes; parameterizable Yes; parameterizable<br />
channels 0 and 2<br />
Diagnostics<br />
- Diagnostic information can be<br />
read out<br />
+/- 0.3 %;<br />
0-6kOhms,0-600kOhms<br />
1 Kelvin<br />
(Pt100,Ni100,standard)<br />
0.8 Kelvin<br />
(Pt100,Ni100,climatic;<br />
Ni1000,LG-Ni1000,<br />
standard; Ni1000,<br />
LG-Ni1000,climatic)<br />
Yes; parameterizable No Yes<br />
Yes Yes No Yes<br />
No<br />
+/- 1 %;<br />
+/-1% (80mV),<br />
+/- 0.6% (250-1000mV),<br />
+/- 0.8% (2.5-10V)<br />
+/- 0.7 %;<br />
from 3.2 to 20mA<br />
+/- 0.7 %;<br />
150, <strong>300</strong>, 600<br />
ohms<br />
+/- 0.7 %;<br />
+/-0.7% (Pt100/ Ni100)<br />
+/-0.8% (Pt100 climat)<br />
+/- 0.6 %;<br />
+/-0.6% (80mV, 2.5-10V)<br />
+/-0.4% (250-1000mV)<br />
+/- 0.5 %; 3.2-20 mA<br />
+/- 0.5 %; 1<br />
50, <strong>300</strong>, 600 ohms<br />
+/- 0.6 %;<br />
+/-0.5% (Pt100/ Ni100)<br />
+/-0.6% (Pt100 climatic)<br />
Yes; parameterizable;<br />
channel 0<br />
4<br />
Siemens ST 70 · 2005<br />
4/61