SIMATIC S7-<strong>300</strong><br />

Analog modules<br />

SM 331 analog input modules<br />

■ Technical specifications (continued)<br />

Sensor<br />

6ES7 331-7KF02-0AB0 6ES7 331-7HF01-0AB0 6ES7 331-1KF01-0AB0 6ES7 331-7KB02-0AB0<br />

Sensing element connection<br />

- for current measurement,<br />

as 2-wire measuring transducer<br />

- for current measurement,<br />

as 4-wire measuring transducer<br />

- for resistance measurement,<br />

with 2-wire connection<br />

- for resistance measurement,<br />

with 3-wire connection<br />

- for resistance measurement,<br />

with 4-wire connection<br />

Error/accuracies<br />

Operational limit in the entire<br />

temperature range<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Basic error limit<br />

(operational limit at 25 °C)<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Yes Yes Yes; with extreme power Yes<br />

supply<br />

Yes Yes Yes Yes<br />

Yes Yes Yes<br />

Yes Yes Yes<br />

Yes Yes Yes<br />

+/- 1 %; +/-1% (80 mV),<br />

+/-0.6% (250-1000 mV),<br />

+/-0.8% (2.5-10 mV)<br />

+/- 0.7 %;<br />

from 3.2 - 20mA<br />

+/- 0.7 %;<br />

50, <strong>300</strong>, 600 ohms<br />

+/- 0.7 %;<br />

+/-0.7% (Pt100/ Ni100)<br />

+/-0.8% (Pt100 climat)<br />

+/- 0.6 %;<br />

+/-0.4% (250-1000mV)<br />

+/-0.6% (2.5-10mV)<br />

+/-0.7% (80mV)<br />

+/- 0.4 % +/- 0.6 %;<br />

+/-0.6%<br />

(+/-5V,10V,1-5V,0-10V;<br />

+/-0.5%<br />

(+/-50mV,500mV,1V<br />

+/- 0.3 % +/- 0.5 %;<br />

+/-20mA,0-20mA,4-20mA<br />

+/- 0.5 %; 0-6kOhms,<br />

0-600kOhms<br />

1 Kelvin<br />

(Pt100,Ni100,climatic;<br />

Ni1000,LG-Ni1000,standard;<br />

Ni1000,LG-<br />

Ni1000,climatic); 1.2<br />

Kelvin (Pt100,Ni100,<br />

standard)<br />

+/- 0.25 % +/- 0.4 %;<br />

0.4%<br />

(+/-5V,10V,1-5V,0-10V);<br />

0.3% (+/ 50mV,500mV,1V)<br />

+/- 0.5 %; 3.2-20 mA +/- 0.2 % +/- 0.3 %;<br />

+/-20mA, 0-20mA, 4-20mA<br />

+/- 0.5 %;<br />

150, <strong>300</strong>, 600 ohms<br />

+/- 0.6 %;<br />

+/-0.5% (Pt100/ Ni100)<br />

+/-0.6% (Pt100 climatic)<br />

Status information/ interrupts/<br />

diagnostics<br />

Interrupts<br />

- Diagnostic interrupt Yes; parameterizable<br />

channels 0 and 2<br />

- Limit value interrupt Yes; parameterizable Yes; parameterizable<br />

channels 0 and 2<br />

Diagnostics<br />

- Diagnostic information can be<br />

read out<br />

+/- 0.3 %;<br />

0-6kOhms,0-600kOhms<br />

1 Kelvin<br />

(Pt100,Ni100,standard)<br />

0.8 Kelvin<br />

(Pt100,Ni100,climatic;<br />

Ni1000,LG-Ni1000,<br />

standard; Ni1000,<br />

LG-Ni1000,climatic)<br />

Yes; parameterizable No Yes<br />

Yes Yes No Yes<br />

No<br />

+/- 1 %;<br />

+/-1% (80mV),<br />

+/- 0.6% (250-1000mV),<br />

+/- 0.8% (2.5-10V)<br />

+/- 0.7 %;<br />

from 3.2 to 20mA<br />

+/- 0.7 %;<br />

150, <strong>300</strong>, 600<br />

ohms<br />

+/- 0.7 %;<br />

+/-0.7% (Pt100/ Ni100)<br />

+/-0.8% (Pt100 climat)<br />

+/- 0.6 %;<br />

+/-0.6% (80mV, 2.5-10V)<br />

+/-0.4% (250-1000mV)<br />

+/- 0.5 %; 3.2-20 mA<br />

+/- 0.5 %; 1<br />

50, <strong>300</strong>, 600 ohms<br />

+/- 0.6 %;<br />

+/-0.5% (Pt100/ Ni100)<br />

+/-0.6% (Pt100 climatic)<br />