■ Technical specifications (continued)<br />

6ES7 635-<br />

2EC01-0AE3<br />

6ES7 635-<br />

2EB01-0AE3<br />

Sensor<br />

Sensing element connection<br />

- for voltage measurement Yes Yes<br />

- for current measurement,<br />

as 2-wire measuring transducer<br />

Yes; with<br />

external<br />

power supply<br />

Yes; with<br />

external<br />

power supply<br />

- for current measurement,<br />

as 4-wire measuring transducer<br />

Yes<br />

Yes<br />

- for resistance measurement,<br />

with 2-wire connection<br />

Yes; without<br />

cable resistance<br />

compensation<br />

No<br />

Yes; without<br />

cable resistance<br />

compensation<br />

No<br />

- for resistance measurement,<br />

with 3-wire connection<br />

- for resistance measurement, No<br />

No<br />

with 4-wire connection<br />

Connectable encoders<br />

- 2-wire BEROS Yes Yes<br />

- permissible closed-circuit 1.5 mA 1.5 mA<br />

current (2-wire BEROS), max.<br />

Error/accuracies<br />

Operational limit in the entire<br />

temperature range<br />

- Relative to the output range, +/- 1 % +/- 1 %<br />

voltage<br />

- Relative to the output range, +/- 1 % +/- 1 %<br />

current<br />

- relative to the input range, +/- 1 % +/- 1 %<br />

voltage<br />

- relative to the input range, +/- 1 % +/- 1 %<br />

current<br />

- relative to the input range, +/- 5 % +/- 5 %<br />

resistance<br />

Basic error limit<br />

(operational limit at 25 °C)<br />

- relative to the output range, +/- 0.7 % +/- 0.7 %<br />

voltage<br />

- relative to the output range, +/- 0.7 % +/- 0.7 %<br />

current<br />

- relative to the input range, +/- 0.7 % +/- 0.7 %<br />

voltage<br />

- relative to the input range, +/- 0.7 % +/- 0.7 %<br />

current<br />

- relative to the input range, +/- 3 % +/- 3 %<br />

resistance<br />

- relative to the input range, +/- 3 % +/- 3 %<br />

resistance thermometer<br />

Interference voltage suppression<br />

for f = n x (fl +/- 1 %)<br />

- Series-mode interference 30 dB 30 dB<br />

(peak value of interference<br />

< rated value input range)<br />

- Common-mode interference, 40 dB 40 dB<br />

min.<br />

Integral functions<br />

• Number of counters 4 4<br />

• Count frequency (counters) max. 60 kHz 60 kHz<br />

• Frequency measurement Yes Yes<br />

• Number of frequency sensors<br />

Frequency<br />

meter up to<br />

max. 60 kHz<br />

Frequency<br />

meter up to<br />

max. 60 kHz<br />

• Controlled positioning Yes Yes<br />

• Integrated function blocks<br />

(control)<br />

Yes;<br />

PID controller<br />

Yes;<br />

PID controller<br />

• PID controller Yes Yes<br />

• Number of pulse outputs<br />

4; Pulse outputs<br />

up to max.<br />

2.5 kHz<br />

4; Pulse outputs<br />

up to max.<br />

2.5 kHz<br />

• Cut-off frequency (pulse) 2.5 kHz 2.5 kHz<br />

SIMATIC C7<br />

Control systems<br />

6ES7 635-<br />

2EC01-0AE3<br />

Status information/ interrupts/<br />

diagnostics<br />

Interrupts<br />

- Interrupts Yes Yes<br />

Operator control and monitoring<br />

• Process pictures Yes Yes<br />

• Graphic objects Yes Yes<br />

• Text elements Yes Yes<br />

• Info texts Yes Yes<br />

• Messages<br />

Yes;<br />

Alarm messages,<br />

event<br />

messages<br />

(no buffer)<br />

C7-635<br />

6ES7 635-<br />

2EB01-0AE3<br />

Yes;<br />

Alarm messages,<br />

event<br />

messages<br />

(no buffer)<br />

• Number of process pictures 100 100<br />

• Number of variables per picture, 50 50<br />

max.<br />

• Number of variables in message 8 8<br />

text, max.<br />

• Password protection Yes Yes<br />

• Password levels 10 10<br />

Keyboard<br />

- Type Touch (resistive/analog)<br />

- Number of operating cycle keys 1,000,000 1,000,000<br />

- Number of function keys 10<br />

- Number of softkey keys 14<br />

Display<br />

- Type STN, CCFL<br />

backlit, 5.7"<br />

Blue Mode<br />

(4 blue levels)<br />

- Background lighting MTBF<br />

(at 20°C)<br />

STN, CCFL<br />

backlit, 5.7"<br />

Blue Mode<br />

(4 blue levels)<br />

50.000 h 50.000 h<br />

Resolution (pixels)<br />

- Width 320 320<br />

- Height 240 240<br />

Event/alarm messages<br />

- Event messages Yes Yes<br />

- Number of entries in process<br />

event buffer, max.<br />

128;<br />

not retentive<br />

- Event messages, max. 2,000; total<br />

number of<br />

event and<br />

alarm messages<br />

- Alarm messages Yes Yes<br />

- Number of alarm messages,<br />

max.<br />

- Number of entries in the alarm<br />

message buffer, max.<br />

2,000; total<br />

number of<br />

event and<br />

alarm<br />

messages<br />

128;<br />

not retentive<br />

Recipes<br />

- Number, max. 20 20<br />

- Data records per recipe, max. 50; limited by<br />

storage<br />

medium<br />

- Entries per data record, max. 60 60<br />

- Recipe data memory, max 32 KByte; can<br />

be extended by<br />

a compact<br />

flash card<br />

(CF card)<br />

128;<br />

not retentive<br />

2,000; total<br />

number of<br />

event and<br />

alarm messages<br />

2,000; total<br />

number of<br />

event and<br />

alarm<br />

messages<br />

128;<br />

not retentive<br />

50; limited by<br />

storage<br />

medium<br />

32 KByte; can<br />

be extended by<br />

a compact<br />

flash card<br />

(CF card)<br />

6<br />

Siemens ST 70 · 2005<br />