■ Technical specifications (continued)<br />

Integrated inputs/outputs<br />

Default addresses of the integral<br />

6ES7 635-<br />

2EC01-0AE3<br />

6ES7 635-<br />

2EB01-0AE3<br />

- Digital inputs 124.0 to 126.7 124.0 to 126.7<br />

- Digital outputs 124.0 to 125.7 124.0 to 125.7<br />

- Analog inputs 752 to 761 752 to 761<br />

- Analog outputs 752 to 755 752 to 755<br />

Digital inputs<br />

• Number of digital inputs 24 24<br />

- which can be used as inputs 16 16<br />

for technological functions<br />

Number of inputs that can be<br />

driven in parallel<br />

• vertical mounting positions<br />

- up to 40°C 18 18<br />

- up to 50°C 12 12<br />

• 45°C mounting positions<br />

- up to 45°C 12 12<br />

• horizontal mounting positions<br />

- up to 40°C 12 12<br />

Length of cable<br />

- Length of cable shielded, max. 1,000 m;<br />

100 m for<br />

technological<br />

functions<br />

- Length of cable unshielded, max. 600 m 600 m<br />

• Technological function<br />

- shielded, max. 50 m;<br />

at maximum<br />

count<br />

frequency<br />

- unshielded, max. Unshielded<br />

cables are not<br />

allowed for<br />

technological<br />

functions<br />

• Standard DI<br />

1,000 m;<br />

100 m for<br />

technological<br />

functions<br />

50 m;<br />

at maximum<br />

count<br />

frequency<br />

Unshielded<br />

cables are not<br />

allowed for<br />

technological<br />

functions<br />

- shielded, max. 1,000 m 1,000 m<br />

- unshielded, max. 600 m 600 m<br />

• Input characteristic to comply Yes<br />

Yes<br />

with IEC 1131, Type 1<br />

Input voltage<br />

- Rated value, DC 24 V 24 V<br />

- for signal "0" -3 to 5 V -3 to 5 V<br />

- for signal "1" 15 to 30 V 15 to 30 V<br />

Input current<br />

- for 1 signal, typical 7 mA 7 mA<br />

Input delay (at rated value of the<br />

input voltage)<br />

• For standard inputs<br />

- Parameterizable Yes;<br />

0.1 / 0.5 / 3 /<br />

5 ms<br />

- Rated value 3 ms 3 ms<br />

• for counters/technological<br />

functions<br />

- at 0 to 1, max. 8 µs 8 µs<br />

Yes;<br />

0.1 / 0.5 / 3 /<br />

15 ms<br />

Digital outputs<br />

SIMATIC C7<br />

Control systems<br />

6ES7 635-<br />

2EC01-0AE3<br />

C7-635<br />

6ES7 635-<br />

2EB01-0AE3<br />

• Number of digital outputs 16 16<br />

- of which fast outputs 4 4<br />

• Length of cable shielded, max. 1,000 m 1,000 m<br />

• Length of cable unshielded, max. 600 m 600 m<br />

• Short-circuit protection of<br />

the output<br />

• Short-circuit prot ection of the output,<br />

response threshold, typical<br />

• Limitation of voltage induced on<br />

circuit interruption to<br />

Yes; clocking<br />

electronically<br />

1 A 1 A<br />

Yes; clocking<br />

electronically<br />

L+ (-48 V) L+ (-48 V)<br />

• Lamp load, max. 5 W 5 W<br />

• Driving a digital input Yes Yes<br />

Output voltage<br />

- for 1 signal L+ (-0.8 V) L+ (-0.8 V)<br />

Output current<br />

- for 1 signal rated value 0.5 A 0.5 A<br />

- permissible range for signal "1", 5 mA 5 mA<br />

min.<br />

- permissible range for signal "1", 0.6 A 0.6 A<br />

max.<br />

- for 1 signal minimum load 5 mA 5 mA<br />

current<br />

- for 0 signal residual current, max. 0.5 mA 0.5 mA<br />

Parallel switching of 2 outputs<br />

- to increase power No No<br />

- to redundantly drive a load Yes Yes<br />

Switching frequency<br />

- at resistive load, max. 100 Hz 100 Hz<br />

- at inductive load, max. 0.5 Hz 0.5 Hz<br />

- at lamp load, max. 100 Hz 100 Hz<br />

- of pulse outputs,<br />

2.5 kHz 2.5 kHz<br />

at resistive load, max.<br />

Summation current of the outputs<br />

(per group)<br />

• vertical mounting positions<br />

- up to 40°C., max. 3 A 3 A<br />

- up to 50°C., max. 2 A 2 A<br />

• 45°C mounting positions<br />

- up to 45°C, max. 2 A 2 A<br />

• horizontal mounting positions<br />

- up to 40°C., max. 2 A 2 A<br />

- up to 40 °C, max. 4 A 4 A<br />

- up to 60 °C, max. 2 A 2 A<br />

Load impedance range<br />

- lower limit 48 Ω 48 Ω<br />

- upper limit 4 kΩ 4 kΩ<br />

6<br />

Siemens ST 70 · 2005<br />

6/17