■ Technical specifications (continued)<br />
Integrated inputs/outputs<br />
Default addresses of the integral<br />
6ES7 635-<br />
2EC01-0AE3<br />
6ES7 635-<br />
2EB01-0AE3<br />
- Digital inputs 124.0 to 126.7 124.0 to 126.7<br />
- Digital outputs 124.0 to 125.7 124.0 to 125.7<br />
- Analog inputs 752 to 761 752 to 761<br />
- Analog outputs 752 to 755 752 to 755<br />
Digital inputs<br />
• Number of digital inputs 24 24<br />
- which can be used as inputs 16 16<br />
for technological functions<br />
Number of inputs that can be<br />
driven in parallel<br />
• vertical mounting positions<br />
- up to 40°C 18 18<br />
- up to 50°C 12 12<br />
• 45°C mounting positions<br />
- up to 45°C 12 12<br />
• horizontal mounting positions<br />
- up to 40°C 12 12<br />
Length of cable<br />
- Length of cable shielded, max. 1,000 m;<br />
100 m for<br />
technological<br />
functions<br />
- Length of cable unshielded, max. 600 m 600 m<br />
• Technological function<br />
- shielded, max. 50 m;<br />
at maximum<br />
count<br />
frequency<br />
- unshielded, max. Unshielded<br />
cables are not<br />
allowed for<br />
technological<br />
functions<br />
• Standard DI<br />
1,000 m;<br />
100 m for<br />
technological<br />
functions<br />
50 m;<br />
at maximum<br />
count<br />
frequency<br />
Unshielded<br />
cables are not<br />
allowed for<br />
technological<br />
functions<br />
- shielded, max. 1,000 m 1,000 m<br />
- unshielded, max. 600 m 600 m<br />
• Input characteristic to comply Yes<br />
Yes<br />
with IEC 1131, Type 1<br />
Input voltage<br />
- Rated value, DC 24 V 24 V<br />
- for signal "0" -3 to 5 V -3 to 5 V<br />
- for signal "1" 15 to 30 V 15 to 30 V<br />
Input current<br />
- for 1 signal, typical 7 mA 7 mA<br />
Input delay (at rated value of the<br />
input voltage)<br />
• For standard inputs<br />
- Parameterizable Yes;<br />
0.1 / 0.5 / 3 /<br />
5 ms<br />
- Rated value 3 ms 3 ms<br />
• for counters/technological<br />
functions<br />
- at 0 to 1, max. 8 µs 8 µs<br />
Yes;<br />
0.1 / 0.5 / 3 /<br />
15 ms<br />
Digital outputs<br />
SIMATIC C7<br />
Control systems<br />
6ES7 635-<br />
2EC01-0AE3<br />
C7-635<br />
6ES7 635-<br />
2EB01-0AE3<br />
• Number of digital outputs 16 16<br />
- of which fast outputs 4 4<br />
• Length of cable shielded, max. 1,000 m 1,000 m<br />
• Length of cable unshielded, max. 600 m 600 m<br />
• Short-circuit protection of<br />
the output<br />
• Short-circuit prot ection of the output,<br />
response threshold, typical<br />
• Limitation of voltage induced on<br />
circuit interruption to<br />
Yes; clocking<br />
electronically<br />
1 A 1 A<br />
Yes; clocking<br />
electronically<br />
L+ (-48 V) L+ (-48 V)<br />
• Lamp load, max. 5 W 5 W<br />
• Driving a digital input Yes Yes<br />
Output voltage<br />
- for 1 signal L+ (-0.8 V) L+ (-0.8 V)<br />
Output current<br />
- for 1 signal rated value 0.5 A 0.5 A<br />
- permissible range for signal "1", 5 mA 5 mA<br />
min.<br />
- permissible range for signal "1", 0.6 A 0.6 A<br />
max.<br />
- for 1 signal minimum load 5 mA 5 mA<br />
current<br />
- for 0 signal residual current, max. 0.5 mA 0.5 mA<br />
Parallel switching of 2 outputs<br />
- to increase power No No<br />
- to redundantly drive a load Yes Yes<br />
Switching frequency<br />
- at resistive load, max. 100 Hz 100 Hz<br />
- at inductive load, max. 0.5 Hz 0.5 Hz<br />
- at lamp load, max. 100 Hz 100 Hz<br />
- of pulse outputs,<br />
2.5 kHz 2.5 kHz<br />
at resistive load, max.<br />
Summation current of the outputs<br />
(per group)<br />
• vertical mounting positions<br />
- up to 40°C., max. 3 A 3 A<br />
- up to 50°C., max. 2 A 2 A<br />
• 45°C mounting positions<br />
- up to 45°C, max. 2 A 2 A<br />
• horizontal mounting positions<br />
- up to 40°C., max. 2 A 2 A<br />
- up to 40 °C, max. 4 A 4 A<br />
- up to 60 °C, max. 2 A 2 A<br />
Load impedance range<br />
- lower limit 48 Ω 48 Ω<br />
- upper limit 4 kΩ 4 kΩ<br />
6<br />
Siemens ST 70 · 2005<br />
6/17