simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SIMATIC C7<br />
Control systems<br />
C7-633<br />
6<br />
■ Technical specifications (continued)<br />
6ES7 633-<br />
1DF02-0AE3<br />
Analog value formation<br />
Integration and conversion<br />
time/triggering per channel<br />
- with over-range<br />
12 Bit<br />
(bits incl. sign), max.<br />
- Conversion time (per channel) 0.5 ms<br />
Settling time<br />
- for resistive load 0.1 ms<br />
- for capacitive load 3.3 ms<br />
- for inductive load 0.5 ms<br />
Universal inputs<br />
• Number of universal inputs 4<br />
• Usable as<br />
UE1 Digital/<br />
alarm input<br />
24V DC or<br />
up/down<br />
counter;<br />
UE2 Digital/<br />
alarm input 24V<br />
DC or up/down<br />
counter;<br />
UE3 Digital/<br />
alarm input 24V<br />
DC or up/down<br />
counter or<br />
frequency/<br />
period duration<br />
counter; UE4<br />
Digital/alarm<br />
input 24 V DC<br />
• Length of cable shielded, max. 1,000 m<br />
• Counter frequency, max.<br />
10 kHz<br />
Input voltage<br />
- Rated value (DC) 24 V<br />
- for 0 signal -3 to 5 V<br />
- for 1 signal 11 to 30 V<br />
Input current<br />
- for 1 signal typ. 11.5 mA<br />
Sensor<br />
Connectable encoders<br />
Yes<br />
- 2-wire BEROS 2 mA<br />
- permissible closed-circuit current<br />
(2-wire BEROS), max.<br />
Error/accuracies<br />
Operational limit in the entire<br />
temperature range<br />
- Relative to the output range,<br />
voltage<br />
- Relative to the output range,<br />
current<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
Basic error limit<br />
(operational limit at 25 °C)<br />
- relative to the output range,<br />
voltage<br />
- relative to the output range,<br />
current<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
+/- 0.8 %<br />
+/- 1 %<br />
+/- 0.8 %<br />
+/- 0.8 %<br />
+/- 0.5 %<br />
+/- 0.6 %<br />
+/- 0.6 %<br />
+/- 0.6 %<br />
6ES7 633-<br />
2BF02-0AE3<br />
6ES7 633-<br />
1DF02-0AE3<br />
Counter<br />
• Number of counter inputs 3;<br />
UE1, UE2, UE3<br />
• Principle<br />
Counting<br />
edges<br />
• Counting range, description UE1, UE2:<br />
up:<br />
0 to 65535,<br />
down:<br />
65535 to 0;<br />
UE3:<br />
up:<br />
0 to 16777215,<br />
down:<br />
16777215 to 0,<br />
• Count interrupt down counter on reaching "0"<br />
• Count interrupt up counter on reaching the<br />
limit value<br />
• Enable<br />
in the program<br />
• Limit value (nominal) default one counter<br />
per value<br />
External gate counter<br />
- Number of external gate 3<br />
counters<br />
- Principle Counting<br />
edges within a<br />
gate time via an<br />
external pin<br />
- Counting range UE1, UE2:<br />
0 to 65535;<br />
UE3:<br />
0 to 16777215<br />
Frequency counter<br />
• Number of frequency counters<br />
1; UE3<br />
• Principle<br />
Counting<br />
pulses within<br />
a time period<br />
• Gate width, adjustable<br />
Yes<br />
• Gate width<br />
0.1 / 1 / 10 s<br />
(adjustable)<br />
• Counting range 0 to 16777215<br />
Period duration counter<br />
• Number<br />
1; UE3<br />
• Period duration, max. 8.38 s;<br />
or 0.12 Hz<br />
• Principle<br />
Counting fixed<br />
time units<br />
between two<br />
positive edges<br />
• Counting range, lower limit 0<br />
• Counting range, upper limit 16.777.214<br />
6ES7 633-<br />
2BF02-0AE3<br />
6/10 Siemens ST 70 · 2005