09.09.2015 Views

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

SIMATIC C7<br />

Control systems<br />

C7-633<br />

■ Technical specifications (continued)<br />

6ES7 633-<br />

1DF02-0AE3<br />

6ES7 633-<br />

2BF02-0AE3<br />

6ES7 633-<br />

1DF02-0AE3<br />

6ES7 633-<br />

2BF02-0AE3<br />

CPU/ programming<br />

Configuration software<br />

- STEP 7 Yes Yes<br />

- STEP 7 Lite Yes Yes<br />

-ProTool Yes Yes<br />

- ProTool/Lite Yes Yes<br />

-ProTool/Pro Yes Yes<br />

Programming language<br />

-LAD Yes Yes<br />

-FBD Yes Yes<br />

-STL Yes Yes<br />

-SCL Yes Yes<br />

-CFC Yes Yes<br />

- GRAPH Yes Yes<br />

- HiGraph ® Yes Yes<br />

Software library<br />

- Process diagnostics Yes; C7-CPU Yes; C7-CPU<br />

- Software controller Yes; 16 circuits Yes; 16 circuits<br />

• Instruction set<br />

see<br />

instruction list<br />

see<br />

instruction list<br />

• Bracket levels 8 8<br />

• User program<br />

Yes<br />

Yes<br />

protection/password protection<br />

• Program organization<br />

linear,<br />

structured<br />

linear,<br />

structured<br />

• System functions (SFC)<br />

see<br />

instruction list<br />

see<br />

instruction list<br />

Cycle time monitoring<br />

- lower limit 1 ms 1 ms<br />

- upper limit 6,000 ms 6,000 ms<br />

- adjustable Yes Yes<br />

- preset 150 ms 150 ms<br />

Digital inputs<br />

• Number of digital inputs 16<br />

Length of cable<br />

- Length of cable shielded, max. 1,000 m<br />

- Length of cable unshielded, 600 m<br />

max.<br />

Input voltage<br />

- Rated value, DC 24 V<br />

- for signal "0" -3 to 5 V<br />

- for signal "1" 11 to 30 V<br />

Input current<br />

- for 1 signal, typical 11.5 mA<br />

Input delay (at rated value<br />

of the input voltage)<br />

• For standard inputs<br />

- at 0 after 1, max. 4.8 ms;<br />

typ. 3 ms<br />

Digital outputs<br />

• Number of digital outputs 16<br />

• Length of cable shielded, max. 1,000 m<br />

• Length of cable unshielded, max. 600 m<br />

• Short-circuit protection of the output<br />

• Limitation of voltage induced on<br />

circuit interruption to<br />

• Lamp load, max.<br />

Yes; clocking<br />

electronically<br />

48 V<br />

5 W<br />

Output voltage<br />

- for 1 signal L+ (-0.8 V)<br />

Output current<br />

- for 1 signal rated value 0.5 A<br />

- for 1 signal minimum<br />

5 mA<br />

load current<br />

- for 0 signal residual current, max. 0.5 mA<br />

Switching frequency<br />

- at resistive load, max. 100 Hz<br />

- at inductive load, max. 0.5 Hz<br />

Summation current of the outputs<br />

(per group)<br />

• horizontal mounting positions<br />

- up to 20 °C, max. 4 A<br />

- up to 40 °C, max. 2 A<br />

Analog inputs<br />

• Number of analog inputs 4<br />

• Permissible input voltage for the 30 V<br />

voltage input (destruction limit),<br />

max.<br />

• Permissible input voltage for the 30 mA<br />

current input (destruction limit),<br />

max.<br />

• Cycle time (all channels), typical 2 ms<br />

Input ranges (rated values),<br />

voltages<br />

- -10 V to +10 V Yes<br />

Input ranges (rated values),<br />

currents<br />

- -20 to +20 mA Yes<br />

- 4 to 20 mA Yes<br />

Analog outputs<br />

• Number of analog outputs 4<br />

• Length of cable shielded, max.<br />

• Voltage output, short-circuit<br />

protection<br />

• Voltage output, short-circuit<br />

current, max<br />

• Current output, open-circuit<br />

voltage, max.<br />

• Cycle time (all channels) max.<br />

200 m<br />

Yes<br />

25 mA<br />

16 V; +/-<br />

4 ms; typ. 2 ms<br />

Output ranges, voltage<br />

- -10 to +10 V Yes<br />

Output ranges, current<br />

- -20 to +20 mA Yes<br />

- 4 to 20 mA Yes<br />

Burden resistance<br />

(in the nominal output range)<br />

- at voltage outputs, min. 2 kOhm<br />

- at voltage outputs,<br />

1 µF<br />

capacitive load, max.<br />

- at current outputs, max. 0.5 kOhm<br />

- at current outputs,<br />

1 mH<br />

inductive load, max.<br />

6<br />

Siemens ST 70 · 2005<br />

6/9