SIMATIC C7<br />

Control systems<br />

C7-613<br />

6<br />

■ Technical specifications (continued)<br />

6ES7 613-1CA01-0AE3<br />

Data areas and<br />

their retentive characteristics<br />

Flags<br />

-Number<br />

256 Byte<br />

- adjustable retentivity Yes; MB 0 bis MB 255<br />

Address area<br />

Process image<br />

- Inputs 128 Byte<br />

-Outputs<br />

128 Byte<br />

Digital channels<br />

- Inputs 992<br />

-Outputs 992<br />

Analog channels<br />

- Inputs 248<br />

-Outputs 124<br />

Configuration<br />

• Number of modules per system, 4<br />

max.<br />

Number of DP masters<br />

- integral 0<br />

- via CP 1<br />

Number of FMs and CPs that can<br />

be operated (recommendation)<br />

-FM 8<br />

- CP, point-to-point 4<br />

- CP, LAN 2<br />

Expansion modules<br />

- Number of expansion modules,<br />

max.<br />

4;<br />

Max. 2 flat alignment,<br />

max. 4 deep alignment<br />

Time<br />

Clock<br />

- Hardware clock (realtime clock) Yes<br />

- buffered Yes<br />

Run-time meter<br />

- Quantity 1<br />

Time synchronization<br />

- supported Yes<br />

S7 message functions<br />

• Number of stations that can log on 5<br />

for message functions, max.<br />

Communication functions<br />

• Number of logical connections 1; fixed with integral CPU<br />

(including the <strong>net</strong>work), max.<br />

• PG/OP communication<br />

Yes<br />

Global data communication<br />

- Number of send GD packets, 4<br />

max.<br />

- Number of receive GD packets, 4<br />

max.<br />

- Size of GD packets, max. 22 Byte<br />

S7 basic communication<br />

- supported Yes<br />

- User data per job 76 Byte<br />

S7 communication<br />

- supported Yes<br />

- User data per job, max. 64 KByte<br />

6ES7 613-1CA01-0AE3<br />

Number of connections<br />

- overall 8<br />

- reserved for PG communication 1<br />

- customizable for PG<br />

7<br />

communication, max.<br />

- reserved for OP communication 1<br />

- customizable for OP<br />

7<br />

communication, max.<br />

- reserved for S7 basic<br />

4<br />

communication<br />

- customizable for S7 basic 4<br />

communication, max.<br />

1st interface<br />

• Isolated<br />

No<br />

Functionality<br />

-MPI<br />

Yes<br />

- DP master No<br />

- DP slave No<br />

MPI<br />

- Number of connections 8<br />

• Services<br />

- PG/OP communication Yes<br />

- Global data communication Yes<br />

- S7 basic communication Yes<br />

- S7 communication Yes<br />

- S7 communication, as client No<br />

- S7 communication, as server Yes<br />

- Transmission rates, max. 187.5 kBit/s<br />

CPU/ programming<br />

Programming language<br />

-LAD<br />

Yes<br />

-FBD<br />

Yes<br />

-STL<br />

Yes<br />

-SCL<br />

Yes<br />

-CFC<br />

Yes<br />

- GRAPH Yes<br />

- HiGraph ® Yes<br />

Software library<br />

• Bracket levels 8<br />

• User program protection/password Yes<br />

protection<br />

Digital inputs<br />

• Number of digital inputs 24<br />

Length of cable<br />

- Length of cable shielded, max. 1,000 m; 100 m for<br />

technological functions<br />

- Length of cable unshielded, max. 600 m<br />

Input voltage<br />

- Rated value, DC 24 V<br />

- for signal "0" -3 to 5 V<br />

- for signal "1" 15 to 30 V<br />

Input current<br />

- for 1 signal, typical 8 mA<br />

Input delay (at rated value of the<br />

input voltage)<br />

• For standard inputs<br />

- Parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms<br />

• for counters/technological<br />

functions<br />

- at 0 to 1, max. 16 µs<br />