09.09.2015 Views

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

simatic s7-300 - megaelektrik.net

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

4<br />

SIMATIC S7-<strong>300</strong><br />

Central processing units<br />

CPU 312C to CPU 317F-2 DP<br />

■ Technical specifications (continued)<br />

6ES7 315-<br />

6FF01-0AB0<br />

6ES7 317-<br />

6FF00-0AB0<br />

1st interface (continued)<br />

DP master<br />

- Number of connections, max. 32<br />

• Services<br />

- PG/OP communication Yes<br />

- Routing Yes<br />

- Global data communication No<br />

- S7 basic communication No<br />

- S7 communication No<br />

- Equidistance support Yes<br />

- SYNC/FREEZE Yes<br />

-DPV1<br />

Yes<br />

- Transmission rates, max. 12 Mbit/s<br />

- Number of DP slaves, max. 125<br />

• Address area<br />

- Inputs, max. 244 KByte<br />

-Outputs, max.<br />

244 KByte<br />

2nd interface<br />

• Type of interface<br />

integrated RS<br />

485 interface<br />

integrated RS<br />

485 interface<br />

• Physical RS 485 RS 485<br />

• Isolated Yes Yes<br />

• Power supply to interface 200 mA 200 mA<br />

(15 to 30 V DC), max.<br />

Functionality<br />

-MPI No No<br />

-DP master Yes Yes<br />

- DP slave Yes Yes<br />

- Point-to-point connection No No<br />

DP master<br />

- Number of connections, max. 16 32<br />

• Services<br />

- PG/OP communication Yes Yes<br />

- Routing Yes Yes<br />

- Global data communication No No<br />

- S7 basic communication No No<br />

- S7 communication No No<br />

- Equidistance support Yes Yes<br />

- SYNC/FREEZE Yes Yes<br />

-DPV1 Yes Yes<br />

- Transmission rates, max. 12 Mbit/s 12 Mbit/s<br />

- Number of DP slaves, max. 125 125<br />

• Address area<br />

- Inputs, max. 244 KByte 244 KByte<br />

-Outputs, max. 244 KByte 244 KByte<br />

6ES7 315-<br />

6FF01-0AB0<br />

2nd interface (continued)<br />

DP slave<br />

- Number of connections 16 32<br />

• Services<br />

- PG/OP communication Yes Yes<br />

- Routing Yes; with active<br />

interface<br />

- Global data communication No No<br />

- S7 basic communication No No<br />

- S7 communication, as client No No<br />

- S7 communication, as server No No<br />

- Direct data exchange<br />

Yes<br />

Yes<br />

(lateral communication)<br />

-DPV1 No No<br />

- GSD file http://www.ad.<br />

siemens.com/<br />

csi_e/gsd<br />

6ES7 317-<br />

6FF00-0AB0<br />

Yes; with active<br />

interface<br />

http://www.ad.<br />

siemens.com/<br />

csi_e/gsd<br />

- Transmission rates, max. 12 Mbit/s 12 Mbit/s<br />

• Intermediate memory<br />

- Inputs 244 Byte 244 Byte<br />

-Outputs 244 Byte 244 Byte<br />

- Address areas, max. 32 32<br />

- User data per address area, 32 Byte 32 Byte<br />

max.<br />

CPU/ programming<br />

Programming language<br />

- STEP 7 Yes; as of V5.1<br />

SP6<br />

-LAD Yes Yes<br />

-FBD Yes Yes<br />

-STL Yes Yes<br />

-SCL Yes Yes<br />

Software library<br />

• Instruction set<br />

See instruction<br />

list<br />

Yes; STEP 7 as<br />

of V 5.2 + SP1<br />

S7 Distributed<br />

Safety as of<br />

V5.2 SP1<br />

See instruction<br />

list<br />

• Bracket levels 8 8<br />

• User program protection/password<br />

Yes<br />

Yes<br />

protection<br />

• System functions (SFC)<br />

See instruction<br />

list<br />

See instruction<br />

list<br />

• System function blocks (SFB)<br />

See instruction<br />

list<br />

See instruction<br />

list<br />

4/34 Siemens ST 70 · 2005