SIMATIC S7-400<br />

Connection methods<br />

Fully modular connection<br />

■ Benefits<br />

5<br />

• Simple plug connections for front connector module, cable<br />

and terminal block<br />

• Fast, low-cost wiring<br />

• Power supply for digital and analog modules can be<br />

connected to the front connector module or terminal block<br />

• Reduction in wiring errors, clear control cabi<strong>net</strong> wiring<br />

• Byte-oriented signal distribution with digital modules<br />

• Each component can be replaced individually<br />

• Any cable length can be configured without waste<br />

■ Technical specifications<br />

Technical specifications for front connector module<br />

Rated operating voltage<br />

24 V DC<br />

Max. permitted operating voltage 60 V DC<br />

Max. permitted continuous current<br />

• per connector pin<br />

1 A<br />

Max. permitted summation current 4 A/byte (voltage infeed)<br />

Permissible ambient air temperature 0 °C to + 60 °C<br />

Test voltage<br />

0.5 kV, 50 Hz, 60 s<br />

Air and creepage distances IEC 664 (1980), IEC 664 A (1981),<br />

in accordance with<br />

DIN VDE 0110 (01.89),<br />

overvoltage class II,<br />

pollution degree 2<br />

Terminal blocks for 1-wire connection and 3-wire initiators<br />

Max. operating voltage<br />

60 V DC<br />

Continuous current per signal 1 A<br />

Max. summation current<br />

4 A/byte<br />

(voltage input)<br />

Operating temperature 0 °C to + 60 °C<br />

Mounting position<br />

Any<br />

Air and creepage distances IEC Report 664, IEC 664 A,<br />

IEC 1131 T2,<br />

CSA C22.2 No 142 UL 508,<br />

VDE 0160 (12.90),<br />

overvoltage category II,<br />

pollution severity 3<br />

Dimensions (W x H x D) in mm<br />

• 1-wire connection<br />

Approx. 51 x 41 x 55<br />

6ES7924-0AA00-_A_0<br />

• For 3-wire initiators<br />

Approx. 60 x 41 x 70<br />

6ES7924-0CA00-_A_0<br />

Terminal blocks with relay 8S<br />

Field circuit side<br />

Coil operating voltage<br />

24 V DC<br />

Input connections<br />

None<br />

Contact side<br />

Number of relay outputs<br />

8 (NO contacts)<br />

Contact design<br />

Single contact, 1 NO<br />

Switching capacity (resistive load) Max. 2 A/250 V AC,<br />

max. 2 A/30 V DC<br />

max. 0.2 A/60 V DC<br />

Recommended minimum load ≥<br />

100 mA<br />

Switching frequency<br />

6 cycles/minute<br />

Service life<br />

• Mechanical<br />

10 x 10 6 switching operations<br />

• Electrical<br />

600 x 10 3 switching operations at<br />

230 V AC/2 A/ power factor = 1<br />

Operating temperature 0 °C to +60 °C<br />

Mounting position<br />

Horizontal, ventilation slots<br />

upwards and downwards.<br />

To permit heat dissipation, a<br />

space of at least 30 mm must be<br />

left above and below the relay terminal<br />

block<br />

Air and creepage distances IEC 1131-2 (1992), EN 50 178<br />

(4/98) overvoltage category III,<br />

pollution severity 2 between trigger<br />

circuit and relay contacts:<br />

5.5 mm between contact groups<br />

K0-K3 and K4-K7: 5.5 mm within<br />

a contact group: 3.2 mm<br />

UL and CSA available soon<br />

Terminal blocks can be removed for<br />

independent wiring<br />

• For 24 V power supply for digital 4-pole terminal block<br />

modules<br />

• For relay outputs<br />

Two 8-pole terminal blocks<br />

Dimensions (W x H x D) in mm Approx. 60 x 68 x 78<br />

6ES7924-0CD00-_A_0<br />

5/90 Siemens ST 70 · 2005