SIMATIC S7-400<br />
Communication<br />
CP 441-1, CP 441-2<br />
■ Overview<br />
• For powerful, high-speed serial communication via point-topoint<br />
connections<br />
• 2 versions:<br />
- CP 441-1 with 1 variable interface for simple point-to-point<br />
connection<br />
- CP 441-2 with 2 variable interfaces for powerful point-topoint<br />
connection<br />
• Plug-in interface modules for different transmission interfaces:<br />
RS 232C (V.24) , 20 mA (TTY) or RS 422/RS 485 (X.27)<br />
• Implemented protocols: ASCII, 3964 (R), printer drivers;<br />
CP 441-2 additionally has RK 512 and customized protocols<br />
(retrofittable)<br />
• Simple parameterization via a parameterization tool integrated<br />
into STEP 7<br />
5<br />
■ Technical specifications<br />
6ES7 441-<br />
1AA03-0AE0<br />
Supply voltages<br />
Rated value<br />
-5 V DC Yes<br />
- 24 V DC Yes<br />
Current consumption<br />
• from backplane bus 5 V DC, max.<br />
Memory/backup<br />
Memory<br />
- Memory requirement per interface<br />
in the S7 CPU<br />
memory card<br />
700 mA; without<br />
interface<br />
module<br />
1 to 5 kBytes<br />
for parameters,<br />
0 to 55 kBytes<br />
for message<br />
texts<br />
6ES7 441-<br />
2AA03-0AE0<br />
700 mA; without<br />
interface<br />
module<br />
1 to 5 kBytes<br />
for parameters,<br />
0 to 55 kBytes<br />
for message<br />
texts,<br />
0 to 64 kBytes<br />
for loadable<br />
drivers<br />
Communication functions<br />
• S7 extended communication Yes Yes<br />
Number of connections<br />
- overall 8 8<br />
Interfaces<br />
• Number 1; variable 2; variable<br />
• Physical interface, 20mA (TTY) Yes Yes<br />
• Physical interface, RS 232C (V.24) Yes Yes<br />
• Physical interface, RS422/RS485 Yes<br />
Yes<br />
(X.27)<br />
• 20mA (TTY), length of cable 1,000 m 1,000 m<br />
(shielded), max.<br />
• RS 232, length of cable (shielded), 10 m 10 m<br />
max.<br />
• RS 422/485, length of cable<br />
(shielded), max.<br />
1,200 m 1,200 m<br />
Interface modules<br />
- 20 mA (TTY), current<br />
consumption from 5 V/24 V, max.<br />
- RS 422/485 (X.27), current<br />
consumption from 5 V, max.<br />
- RS232C (V.24), current<br />
consumption from 5 V, max.<br />
<strong>300</strong> mA at 5 V,<br />
45 mA at 24 V<br />
<strong>300</strong> mA at 5 V,<br />
45 mA at 24 V<br />
<strong>300</strong> mA <strong>300</strong> mA<br />
<strong>300</strong> mA <strong>300</strong> mA<br />
Point-to-point<br />
• Supported printers<br />
6ES7 441-<br />
1AA03-0AE0<br />
HP-Deskjet,<br />
HP-Laserjet,<br />
IBM-Proprinter,<br />
user-defined<br />
6ES7 441-<br />
2AA03-0AE0<br />
HP-Deskjet,<br />
HP-Laserjet,<br />
IBM-Proprinter,<br />
user-defined<br />
• Transmission rate, max. 38.4 kBit/s 115.2 kBit/s;<br />
split between<br />
both interfaces<br />
Integral protocol driver<br />
- 3964 (R) Yes Yes<br />
-ASCII Yes Yes<br />
- Printer Yes Yes<br />
- Customer-specific drivers<br />
Yes<br />
for later loading<br />
-RK512<br />
Yes<br />
Transmission rate, 20 mA (TTY)<br />
- with 3964 (R) protocol, max. 19.2 kBit/s 19.2 kBit/s<br />
- with ASCII protocol, max. 19.2 kBit/s 19.2 kBit/s<br />
- with printer driver, max. 19.2 kBit/s 19.2 kBit/s<br />
- with RK 512 protocol, max. 19.2 kBit/s<br />
Transmission rate, RS 422/485<br />
- with 3964 (R) protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
- with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
- with printer driver, max. 38.4 kBit/s 115.2 kBit/s<br />
- with RK 512 protocol, max. 115.2 kBit/s<br />
Transmission rate, RS232<br />
- with 3964 (R) protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
- with ASCII protocol, max. 38.4 kBit/s 115.2 kBit/s<br />
- with printer driver, max. 38.4 kBit/s 115.2 kBit/s<br />
- with RK 512 protocol, max. 115.2 kBit/s<br />
CPU/ programming<br />
Configuration software<br />
- STEP 7 Yes; separate<br />
parameterization<br />
masks<br />
Yes; separate<br />
parameterization<br />
masks<br />
Siemens ST 70 · 2005<br />
5/71