SIMATIC S7-400<br />

Function modules<br />

Accessories for FM 458-1 DP<br />

■ Overview SU12 interface module<br />

■ Overview SU13 interface module<br />

5<br />

The interface module is used to connect 10 signals; there is no<br />

electronic conversion.<br />

This interface module can be used to connect 50 signals; there<br />

is no electronic conversion.<br />

■ Technical specifications<br />

SB 10 interface module<br />

Number of digital inputs or outputs 8<br />

Electrical isolation<br />

No<br />

Max. cable cross-section 1.5 mm 2<br />

Dimensions (W x H x D) in mm 45 x 130 x 156<br />

Weight<br />

0.3 kg<br />

SB60 interface module<br />

Number of digital inputs for 8<br />

• Input voltage<br />

115/230 V DC/AC<br />

Electrical isolation<br />

Yes, via optocoupler<br />

Insulation voltage<br />

Separation assured:<br />

• Isolation between inputs and<br />

outputs assured<br />

• 1125 V AC test voltage for input<br />

current circuit<br />

Max. cable cross-section 1.5 mm 2<br />

Dimensions (W x H x D) in mm 45 x 130 x 156<br />

Weight<br />

0.31 kg<br />

SB61 interface module<br />

Number of digital inputs for 8<br />

• Input voltage<br />

24/48 V DC<br />

Electrical isolation<br />

Yes, via optocoupler<br />

Max. cable cross-section 1.5 mm 2<br />

Dimensions (W x H x D) in mm 45 x 130 x 156<br />

Weight<br />

0.32 kg<br />

SB70 interface module<br />

Number of digital outputs 8<br />

• Output voltage, max<br />

120 V DC/AC<br />

Relay switching current<br />

• For 120 V AC<br />

2 A<br />

• For 120 V DC<br />

0.2 A<br />

Electrical isolation<br />

Using relay<br />

Isolation voltage<br />

Separation assured:<br />

• Isolation between inputs and<br />

outputs assured<br />

• 1125 V AC test voltage for input<br />

current circuits<br />

Max. cable cross-section 1.5 mm 2<br />

Dimensions (W x H x D) in mm 45 x 130 x 156<br />

Weight<br />

0.32 kg<br />

SB71 interface module<br />

Number of digital outputs 8<br />

• Output voltage, max<br />

24/48 V DC<br />

Output current, max.<br />

40 mA, short-circuit proof<br />

Electrical isolation<br />

Yes, via optocoupler<br />

Max. cable cross-section 1.5 mm 2<br />

Dimensions (W x H x D) in mm 45 x 130 x 156<br />

Weight<br />

0.32 kg<br />