■ Technical specifications (continued)<br />

6ES7 317-<br />

2EJ10-0AB0<br />

Communication functions<br />

(continued)<br />

PROFINET CBA (at 50 % Communication<br />

Load)<br />

- Number of remote interconnection<br />

nodes<br />

32<br />

- Sum of all Master/Slave connectors<br />

1,000<br />

- Data length of all input Master/Slave<br />

connectors<br />

4,000 Byte<br />

- Data length of all output Master/Slave<br />

connectors<br />

4,000 Byte<br />

- Data length for arrays and structures<br />

(acyclic interconnection),<br />

1,400 Byte<br />

max.<br />

- Data length for arrays and structures<br />

(cyclic interconnection),<br />

450 Byte<br />

max.<br />

- Data length for arrays and structures<br />

(local interconnection),<br />

max.<br />

128 Byte;<br />

Slave-dependent<br />

• Remote interconnections with acyclic<br />

transmission<br />

- Sample frequency: sample interval,<br />

min.<br />

500 ms<br />

- Number of input interconnections<br />

100<br />

- Number of output interconnections<br />

100<br />

- Data length of all input interconnections<br />

2,000 Byte<br />

- Data length of all output interconnections<br />

2,000 Byte<br />

• Remote interconnections with cyclic<br />

transmission<br />

- Transmission frequency: transmission<br />

interval, min.<br />

10 ms<br />

- Number of input interconnections<br />

200<br />

- Number of output interconnections<br />

200<br />

- Data length of all input interconnections<br />

2,000 Byte<br />

- Data length of all output interconnections<br />

2,000 Byte<br />

• HMI variables via PROFINET (acyclic)<br />

- Update HMI variables 500 ms<br />

- Number of HMI variables 200<br />

- Data length of all HMI variables 2,000 Byte<br />

• PROFIBUS Proxy Functionality<br />

- supports Yes<br />

- Number of coupled PROFIBUS<br />

devices<br />

16<br />

- Number of device internals and<br />

PROFIBUS interconnections<br />

500<br />

- Data length of all device internals<br />

and PROFIBUS interconnections<br />

1st interface<br />

• Type of interface<br />

4,000 Byte<br />

integrated RS<br />

485 interface<br />

6ES7 317-<br />

6TJ10-0AB0<br />

integrated RS<br />

485 interface<br />

• Physical RS 485 RS 485<br />

• Isolated Yes Yes<br />

• Power supply to interface (15 to 30<br />

V DC), max.<br />

200 mA 200 mA<br />

SIMATIC S7-<strong>300</strong><br />

Central processing units<br />

CPU 312C to CPU 317F-2 DP<br />

6ES7 317-<br />

2EJ10-0AB0<br />

Functionality<br />

-MPI Yes Yes<br />

- DP master<br />

Yes<br />

Yes<br />

- DP slave<br />

Yes<br />

Yes<br />

- Point-to-point connection<br />

No<br />

No<br />

MPI<br />

- Number of connections 16<br />

• Services<br />

- PG/OP communication Yes Yes<br />

- Routing<br />

Yes<br />

Yes<br />

- Global data communication Yes Yes<br />

- S7 basic communication<br />

Yes<br />

Yes<br />

- S7 communication<br />

Yes<br />

Yes<br />

- S7 communication, as client<br />

No; via CP and<br />

loadable FB<br />

Yes<br />

6ES7 317-<br />

6TJ10-0AB0<br />

Yes; via CP and<br />

loadable FB<br />

Yes<br />

- S7 communication, as server<br />

- Transmission rates, max.<br />

12 Mbit/s 12 Mbit/s<br />

DP master<br />

• Services<br />

- PG/OP communication Yes Yes<br />

- Routing<br />

Yes<br />

Yes<br />

- Global data communication<br />

No<br />

No<br />

- S7 basic communication<br />

No<br />

No<br />

- S7 communication<br />

No<br />

No<br />

- Equidistance support<br />

Yes<br />

Yes<br />

- SYNC/FREEZE Yes Yes<br />

-DPV1<br />

Yes<br />

Yes<br />

- Transmission rates, max. 12 Mbit/s 12 Mbit/s<br />

- Number of DP slaves, max.<br />

124 124<br />

• Address area<br />

- Inputs, max. 244 KByte 244 KByte<br />

- Outputs, max.<br />

244 KByte 244 KByte<br />

DP slave<br />

• Services<br />

- Routing Yes; with active Yes<br />

interface<br />

- Global data communication No No<br />

- S7 Basic communication<br />

No<br />

No<br />

- S7 communication No No<br />

- Direct data exchange (lateral<br />

communication)<br />

Yes<br />

Yes<br />

-DPV1 No No<br />

- Transmission rates, max.<br />

12 Mbit/s 12 Mbit/s<br />

• Intermediate memory<br />

- Inputs 244 Byte 244 Byte<br />

-Outputs<br />

244 Byte 244 Byte<br />

- Address areas, max.<br />

32 32<br />

- User data per address area,<br />

max.<br />

32 Byte 32 Byte<br />

4<br />

Siemens ST 70 · 2005<br />

4/29