SIMATIC S7-<strong>300</strong><br />
Central processing units<br />
CPU 312C to CPU 317F-2 DP<br />
■ Technical specifications (continued)<br />
6ES7 317-<br />
2EJ10-0AB0<br />
6ES7 317-<br />
6TJ10-0AB0<br />
Process image<br />
- Inputs 256 Byte 256 Byte<br />
-Outputs<br />
256 Byte 256 Byte<br />
- Inputs, adjustable<br />
2,048 KByte<br />
- Outputs, adjustable 2,048 KByte<br />
- Inputs, preset 256 Byte<br />
- Outputs, preset 256 Byte<br />
Digital channels<br />
- Inputs 65,536 65,636<br />
-Outputs<br />
65,536 65,636<br />
- Inputs, of which central 1.024 256<br />
- Outputs, of which central<br />
1.024 256<br />
Analog channels<br />
- Inputs 4,096 4,096<br />
-Outputs<br />
4,096 4,096<br />
- Inputs, of which central<br />
256 64<br />
- Outputs, of which central<br />
256 64<br />
Configuration<br />
• Racks, max. 4 1<br />
• Modules per rack, max. 8 8<br />
Number of DP masters<br />
- integral 1 2<br />
- via CP 4 2<br />
Number of FMs and CPs that can<br />
be operated (recommendation)<br />
-FM 8 8<br />
- CP, point-to-point<br />
8 8<br />
- CP, LAN 10 10<br />
Time<br />
Clock<br />
- Hardware clock (realtime clock) Yes Yes<br />
- buffered<br />
Yes<br />
Yes<br />
- Deviation per day, max<br />
10 s 10 s<br />
Run-time meter<br />
- Quantity 4 4<br />
-Number 0 to 3 0 to 3<br />
- Range of values<br />
0 to 2^31 hours<br />
(when using<br />
SFC 101)<br />
0 to 2^31 hours<br />
(when using<br />
SFC 101)<br />
- Granularity<br />
1 hour 1 hour<br />
- retentive<br />
Yes; must be<br />
restarted on<br />
each complete<br />
restart<br />
Time synchronization<br />
- supported Yes Yes<br />
- on MPI, master<br />
Yes<br />
Yes<br />
- on MPI, slave<br />
Yes<br />
Yes<br />
- in AS, master<br />
Yes<br />
Yes<br />
- in AS, slave<br />
Yes<br />
Yes<br />
Yes; must be<br />
restarted on<br />
each complete<br />
restart<br />
S7 message functions<br />
• Number of stations that can log on<br />
for message functions, max.<br />
6ES7 317-<br />
2EJ10-0AB0<br />
32; depending<br />
on the connections<br />
configured<br />
for PG/OP<br />
and S7 basic<br />
communication<br />
6ES7 317-<br />
6TJ10-0AB0<br />
32; depending<br />
on the connections<br />
configured<br />
for PG/OP<br />
and S7 basic<br />
communication<br />
• Process diagnostic messages Yes Yes<br />
• simultaneously active Alarm-S 60 60<br />
blocks, max.<br />
Test and startup functions<br />
Status/modify<br />
- Variable Yes Yes<br />
- Variables<br />
Inputs, outputs,<br />
flags, DB,<br />
timers,<br />
counters<br />
Inputs, outputs,<br />
flags, DB,<br />
timers,<br />
counters<br />
- Number of variables, max.<br />
30 30<br />
- of which status variables, max.<br />
30 30<br />
- of which modify variables, max.<br />
14 14<br />
Forcing<br />
- Forcing Yes Yes<br />
- Forcing, variables<br />
Inputs, outputs Inputs, outputs<br />
- Forcing, number of variables,<br />
max.<br />
10 10<br />
• Status block Yes Yes<br />
• Single step Yes Yes<br />
• Number of breakpoints 2 2<br />
Diagnostic buffer<br />
- available Yes Yes<br />
- Number of inputs, max.<br />
100 100<br />
- adjustable<br />
No<br />
Communication functions<br />
• PG/OP communication Yes Yes<br />
• Routing Yes Yes<br />
Global data communication<br />
- supported Yes Yes<br />
- Size of GD packets, max.<br />
22 Byte 22 Byte<br />
S7 basic communication<br />
- supported Yes Yes<br />
S7 communication<br />
- supported Yes Yes<br />
S5 compatible communication<br />
- supported Yes; via CP and<br />
loadable FC<br />
Yes; via CP and<br />
loadable FC<br />
Standard communication<br />
- TCP/IP Yes<br />
- Number of connections, max. 8<br />
- Data length, max. 1.460 Byte<br />
Number of connections<br />
- overall 32 32<br />
- usable for PG communication<br />
31 31<br />
- usable for OP communication<br />
31 31<br />
- usable for S7 basic<br />
communication<br />
30 31<br />
4/28 Siemens ST 70 · 2005