SIMATIC S7-400<br />

Analog modules<br />

Analog input SM 431<br />

■ Technical specifications (continued)<br />

6ES7 431-7QH00-0AB0 6ES7 431-7KF00-0AB0 6ES7 431-7KF10-0AB0<br />

Input ranges (rated values),<br />

resistances<br />

- 0 to 150 ohms Yes<br />

- 0 to <strong>300</strong> ohms Yes<br />

- 0 to 48 ohms Yes<br />

- 0 to 600 ohms Yes<br />

- 0 to 6000 ohms Yes; effective to 5000 ohms<br />

Input ranges (rated values),<br />

resistance thermometer<br />

-Ni 100 Yes Yes<br />

- Ni 1000 Yes Yes<br />

- Pt 100 Yes Yes<br />

- Pt 1000 Yes Yes<br />

- Pt 200 Yes Yes<br />

- Pt 500 Yes Yes<br />

5<br />

Characteristic curve linearization<br />

- parameterizable Yes Yes Yes<br />

- for thermocouples Type B, R, S, T, E, J, K, N, U, L Type B, N, E, R, S, J, L, T, K, U<br />

- for resistance thermometer Pt 100, Pt 200, Pt 500, Pt 1000,<br />

Ni 100, Ni 1000<br />

Pt 100, Pt 200, Pt 500, Pt 1000,<br />

Ni 100, Ni 1000 choice of<br />

different characteristic<br />

(Europe/US)<br />

Temperature compensation<br />

- external temperature<br />

Yes<br />

Yes<br />

compensation with<br />

compensating box possible<br />

- external temperature<br />

Yes<br />

compensation with Pt100<br />

- internal temperature<br />

Yes<br />

compensation possible<br />

- dynamic reference<br />

Yes<br />

Yes<br />

temperature value<br />

Analog value formation<br />

Integration and conversion<br />

time/triggering per channel<br />

- with over-range (bits incl. sign), 16 Bit 16 Bit 16 Bit<br />

max<br />

- Integration time parameterizable Yes<br />

- Integration time, ms 2.5 / 16.67 / 20 ms 20 ms at 50 Hz (ent. module) 20 ms at 50 Hz (ent. module<br />

incl. wire break)<br />

- Basic conversion time, ms 6 / 21.1 / 23.5 ms<br />

- Additional conversion time 4.3 ms<br />

for wire break monitoring<br />

- Add´l conv. time for wire break 5.5 ms 1 ms (mod.) no<br />

monitoring and resistance meas.<br />

- Additional conversion time 12 / 40.2 / 47 ms<br />

for resistance measurement<br />

- Interference voltage<br />

suppression for interference<br />

frequency f1 in Hz<br />

400 / 60 / 50 Hz 400 / 60 / 50 Hz 60 / 50 Hz<br />

Sensor<br />

Sensing element connection<br />

- for current measurement,<br />

as 2-wire measuring transducer<br />

- for current measurement,<br />

as 4-wire measuring transducer<br />

- for resistance measurement,<br />

with 2-wire connection<br />

- for resistance measurement,<br />

with 3-wire connection<br />

- for resistance measurement,<br />

with 4-wire connection<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

Yes Yes Yes<br />

Yes<br />

Siemens ST 70 · 2005<br />