simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SIMATIC S7-400<br />
Analog modules<br />
Analog input SM 431<br />
■ Technical specifications (continued)<br />
6ES7 431-0HH00-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0 6ES7 431-1KF20-0AB0<br />
Sensor<br />
Sensing element connection<br />
- for current measurement,<br />
as 2-wire measuring transducer<br />
- for current measurement,<br />
as 4-wire measuring transducer<br />
- for resistance measurement,<br />
with 2-wire connection<br />
- for resistance measurement,<br />
with 3-wire connection<br />
- for resistance measurement,<br />
with 4-wire connection<br />
Error/accuracies<br />
Operational limit in the entire<br />
temperature range<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
- relative to the input range,<br />
resistance<br />
- relative to the input range,<br />
resistance thermometer<br />
Basic error limit<br />
(operational limit at 25 °C)<br />
- relative to the input range,<br />
voltage<br />
- relative to the input range,<br />
current<br />
- relative to the input range,<br />
resistance<br />
- relative to the input range,<br />
resistance thermometer<br />
Insulation<br />
• Insulation tested with<br />
Yes<br />
Yes; with external power Yes<br />
Yes<br />
supply<br />
Yes Yes Yes Yes<br />
Yes Yes Yes<br />
Yes<br />
Yes<br />
Yes Yes Yes<br />
+/- 0.65 %;<br />
+/- 1.25 % +/- 0.5 % +/- 0.9 %<br />
1.0% at 1 to 5 V<br />
+/- 0.65 % +/- 1.25 % +/- 0.5 % +/- 0.9 %<br />
+/- 1.25 % +/- 0.5 % +/- 0.9 %<br />
+/- 0.5 %<br />
+/- 0.25 %; 0.5% at 1 to +/- 0.8 % +/- 0.3 % +/- 0.75 %<br />
5 V<br />
+/- 0.25 % +/- 0.8 % +/- 0.3 % +/- 0.75 %<br />
1500 V AC between bus<br />
and analog section<br />
+/- 0.8 % +/- 0.3 % +/- 0.75 %<br />
1500 V AC between bus<br />
and analog section<br />
+/- 0.3 %<br />
1500 V AC between bus<br />
and analog section<br />
1500 V AC between bus<br />
and analog section<br />
Potentials/ electrical isolation<br />
Analog output functions<br />
- Electrical isolation,<br />
No Yes; internal/external Yes; internal/external Yes; internal/external<br />
analog inputs<br />
- between the channels No No No No<br />
Permissible potential difference<br />
• between the inputs (UCM) 8 V AC 30 V AC 120 V AC 8 V AC<br />
Dimensions and weight<br />
• Weight, approx. 500 g 480 g 500 g 500 g<br />
• Width 25 mm 25 mm 25 mm 25 mm<br />
• Height 290 mm 290 mm 290 mm 290 mm<br />
•Depth 210 mm 210 mm 210 mm 210 mm<br />
• Required slots 1 1 1 1<br />
5<br />
Siemens ST 70 · 2005<br />
5/39