SIMATIC S7-400<br />

Analog modules<br />

Analog input SM 431<br />

■ Technical specifications (continued)<br />

6ES7 431-0HH00-0AB0 6ES7 431-1KF00-0AB0 6ES7 431-1KF10-0AB0 6ES7 431-1KF20-0AB0<br />

Sensor<br />

Sensing element connection<br />

- for current measurement,<br />

as 2-wire measuring transducer<br />

- for current measurement,<br />

as 4-wire measuring transducer<br />

- for resistance measurement,<br />

with 2-wire connection<br />

- for resistance measurement,<br />

with 3-wire connection<br />

- for resistance measurement,<br />

with 4-wire connection<br />

Error/accuracies<br />

Operational limit in the entire<br />

temperature range<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Basic error limit<br />

(operational limit at 25 °C)<br />

- relative to the input range,<br />

voltage<br />

- relative to the input range,<br />

current<br />

- relative to the input range,<br />

resistance<br />

- relative to the input range,<br />

resistance thermometer<br />

Insulation<br />

• Insulation tested with<br />

Yes<br />

Yes; with external power Yes<br />

Yes<br />

supply<br />

Yes Yes Yes Yes<br />

Yes Yes Yes<br />

Yes<br />

Yes<br />

Yes Yes Yes<br />

+/- 0.65 %;<br />

+/- 1.25 % +/- 0.5 % +/- 0.9 %<br />

1.0% at 1 to 5 V<br />

+/- 0.65 % +/- 1.25 % +/- 0.5 % +/- 0.9 %<br />

+/- 1.25 % +/- 0.5 % +/- 0.9 %<br />

+/- 0.5 %<br />

+/- 0.25 %; 0.5% at 1 to +/- 0.8 % +/- 0.3 % +/- 0.75 %<br />

5 V<br />

+/- 0.25 % +/- 0.8 % +/- 0.3 % +/- 0.75 %<br />

1500 V AC between bus<br />

and analog section<br />

+/- 0.8 % +/- 0.3 % +/- 0.75 %<br />

1500 V AC between bus<br />

and analog section<br />

+/- 0.3 %<br />

1500 V AC between bus<br />

and analog section<br />

1500 V AC between bus<br />

and analog section<br />

Potentials/ electrical isolation<br />

Analog output functions<br />

- Electrical isolation,<br />

No Yes; internal/external Yes; internal/external Yes; internal/external<br />

analog inputs<br />

- between the channels No No No No<br />

Permissible potential difference<br />

• between the inputs (UCM) 8 V AC 30 V AC 120 V AC 8 V AC<br />

Dimensions and weight<br />

• Weight, approx. 500 g 480 g 500 g 500 g<br />

• Width 25 mm 25 mm 25 mm 25 mm<br />

• Height 290 mm 290 mm 290 mm 290 mm<br />

•Depth 210 mm 210 mm 210 mm 210 mm<br />

• Required slots 1 1 1 1<br />

5<br />

Siemens ST 70 · 2005<br />

5/39