SIMATIC S7-400<br />

Digital modules<br />

Digital output SM 422<br />

■ Overview<br />

• Digital outputs for the SIMATIC S7-400<br />

• For connecting solenoid va lves, contactors, low-power<br />

motors, lamps and motor starters<br />

5<br />

■ Technical specifications<br />

6ES7 422-<br />

1FH00-0AA0<br />

6ES7 422-<br />

1HH00-0AA0<br />

6ES7 422-<br />

1BH11-0AA0<br />

6ES7 422-<br />

1BL00-0AA0<br />

6ES7 422-<br />

7BL00-0AB0<br />

Voltages and currents<br />

Load voltage L+<br />

- Rated value (DC) 60 V 24 V 24 V 24 V<br />

- permissible range,<br />

1 V 20.4 V 20.4 V 20.4 V<br />

lower limit (DC)<br />

- permissible range,<br />

60 V 28.8 V 28.8 V 28.8 V<br />

upper limit (DC)<br />

Load voltage L1<br />

- Rated value (AC) 120/230 V AC 230 V<br />

- permissible range,<br />

79 V 2 V<br />

lower limit (AC)<br />

- permissible range,<br />

264 V 264 V<br />

upper limit (AC)<br />

Current consumption<br />

• from load voltage L+ (no load),<br />

30 mA 30 mA 120 mA<br />

max.<br />

• from load voltage L1 (no load), 6 mA<br />

max.<br />

• from backplane bus 5 V DC, max. 400 mA 1 A 160 mA 200 mA 200 mA<br />

• Power dissipation, max. 16 W 25 W 7 W 4 W 8 W<br />

Digital outputs<br />

• Number of digital outputs 16 16; Relay 16 32 32<br />

• Length of cable shielded, max. 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m<br />

• Length of cable unshielded, max. 600 m 600 m 600 m 600 m 600 m<br />

• Short-circuit protection<br />

of the output<br />

• Limitation of voltage induced<br />

on circuit interruption to<br />

Yes; Fusing<br />

Yes; clocking<br />

electronically<br />

Yes; clocking<br />

electronically<br />

Yes; clocking<br />

electronically<br />

-30 V -27 V L+ (-45 V)<br />

• Lamp load, max. 25 W 10 W 5 W 5 W<br />

Output voltage<br />

- for 1 signal L1 (-18.1 V) L+ (-0.5 V) L+ (-0.3 V) L+ (-0.8 V)<br />

Output current<br />

- for 1 signal rated value 2 A 2 A 0.5 A 0.5 A<br />

- for 1 signal permissible range 10 mA 5 mA 5 mA 5 mA<br />

for 0 to 60 °C, min.<br />

- for 1 signal permissible range 2 A 2.4 A 0.6 A 0.6 A<br />

for 0 to 60 °C, max.<br />

- for 0 signal residual current, max. 2.6 mA 0.5 mA 0.3 mA 0.5 mA<br />