SIMATIC S7-400<br />
Central processing units<br />
CPU 416F-2<br />
5<br />
■ Technical specifications (continued)<br />
6ES7 416-2FK02-0AB0<br />
S5 compatible communication<br />
- supported Yes; via CP and FC AG_SEND<br />
and FC AG_RECV<br />
- User data per job, max. 8 KByte<br />
Standard communication<br />
- Supported Yes; via CP and loadable FB<br />
Number of connections<br />
- overall 64<br />
1st interface<br />
• Physical<br />
RS 485 / PROFIBUS<br />
• Isolated<br />
Yes<br />
Functionality<br />
-MPI<br />
Yes<br />
-DP master<br />
Yes<br />
- DP slave Yes<br />
MPI<br />
- Number of connections 44<br />
• Services<br />
- PG/OP communication Yes<br />
- Routing Yes<br />
- Global data communication Yes<br />
- S7 basic communication Yes<br />
- S7 communication Yes<br />
- Transmission rates, max. 12 Mbit/s<br />
DP master<br />
- Number of connections, max. 32<br />
• Services<br />
- PG/OP communication Yes<br />
- Routing Yes<br />
- S7 basic communication No<br />
- S7 communication Yes<br />
- Equidistance support Yes<br />
- Activate/deactivate DP slaves Yes<br />
- Direct data exchange<br />
Yes<br />
(lateral communication)<br />
- Transmission rates, max. 12 Mbit/s<br />
- Number of DP slaves, max. 32<br />
• User data per DP Slave<br />
- Inputs, max. 244 Byte<br />
-Outputs, max.<br />
244 Byte<br />
DP slave<br />
• Services<br />
- Routing Yes; with active interface<br />
- Status/modify Yes; with active interface<br />
- Programming Yes; with active interface<br />
- Transmission rates, max. 12 Mbit/s<br />
• Intermediate memory<br />
- Address areas, max. 32<br />
- User data per address area, 32 Byte<br />
max.<br />
- User data per address area, 32 Byte<br />
of which consistent, max.<br />
6ES7 416-2FK02-0AB0<br />
2nd interface<br />
• Physical<br />
RS 485 / PROFIBUS<br />
• Isolated<br />
Yes<br />
Functionality<br />
- DP master Yes<br />
- DP slave Yes<br />
DP master<br />
- Number of connections, max. 32<br />
• Services<br />
- PG/OP communication Yes<br />
- Routing Yes<br />
- S7 basic communication No<br />
- S7 communication Yes<br />
- Equidistance support Yes<br />
- Activate/deactivate DP slaves Yes<br />
- Direct data exchange<br />
Yes<br />
(lateral communication)<br />
- Transmission rates, max. 12 Mbit/s<br />
- Number of DP slaves, max. 125<br />
• Address area<br />
- Inputs, max. 8 KByte<br />
- Outputs, max. 8 KByte<br />
• User data per DP Slave<br />
- Inputs, max. 128 Byte<br />
- Outputs, max. 128 Byte<br />
DP slave<br />
• Services<br />
- Routing Yes; with active interface<br />
- Status/modify Yes; with active interface<br />
- Programming Yes; with active interface<br />
- Transmission rates, max. 12 Mbit/s<br />
• Intermediate memory<br />
- Inputs 244 Byte<br />
-Outputs<br />
244 Byte<br />
- Address areas, max. 32<br />
- User data per address area, 32 Byte<br />
max.<br />
- User data per address area, 32 Byte<br />
of which consistent, max.<br />
Clock synchronism<br />
• User data per clock synchronous 128 Byte<br />
slave, max.<br />
• Equidistance<br />
Yes<br />
• Shortest clock pulse<br />
5 ms; 2.5 ms without using<br />
SFCs 126 / 127<br />
CiR configuration in RUN<br />
• CiR synchronization time,<br />
100 ms<br />
base load<br />
• CiR synchronization time,<br />
120 µs<br />
time per I/O slave<br />
5/26 Siemens ST 70 · 2005