SIMATIC S7-400<br />

Central processing units<br />

CPU 416F-2<br />

■ Technical specifications (continued)<br />

Data areas and their retentive<br />

characteristics<br />

• Retentive data area as a whole<br />

6ES7 416-2FK02-0AB0<br />

total working and load memory<br />

(with backup battery)<br />

Flags<br />

-Number<br />

16 KByte<br />

- adjustable retentivity Yes; MB 0 to MB 16383<br />

- Number of clock memories 8; 1 memory byte<br />

Address area<br />

I/O address area<br />

- Inputs 16 KByte<br />

-Outputs<br />

16 KByte<br />

• of which distributed<br />

- MPI/DP interface, inputs 2 KByte<br />

- MPI/DP interface, outputs 2 KByte<br />

- DP interface, inputs 8 KByte<br />

- DP interface, outputs 8 KByte<br />

Process image<br />

- Inputs, adjustable 16 KByte<br />

- Outputs, adjustable 16 KByte<br />

- Inputs, preset 512 Byte<br />

- Outputs, preset 512 Byte<br />

- Number of component process 8<br />

images, max.<br />

- Access to consistent data Yes<br />

in the process image<br />

- Consistent data, max. 244 Byte<br />

Digital channels<br />

- Inputs 131,072<br />

-Outputs 131,072<br />

- Inputs, of which central 131,072<br />

- Outputs, of which central 131,072<br />

Analog channels<br />

- Inputs 8,192<br />

-Outputs 8,192<br />

- Inputs, of which central 8,192<br />

- Outputs, of which central 8,192<br />

Configuration<br />

• connectable OP<br />

63 without event processing,<br />

12 with event processing<br />

• Central units, max. 1<br />

• Expansion units, max. 21<br />

• Multi-computing<br />

Yes; max. 4 CPUs (with UR1 or<br />

UR2)<br />

IM<br />

- Number of pluggable IMs 6<br />

(overall), max.<br />

- Number of pluggable IM 460s, 6<br />

max.<br />

- Number of pluggable IM 463s, 4<br />

max.<br />

Number of DP masters<br />

- integral 2<br />

- via IM 467 4<br />

- via CP 10; CP 443-5 Ext.<br />

- Mixed mode of IM + CP<br />

permitted<br />

- via interface module 0<br />

- No. pluggable S5 modules 6<br />

(via adapter casing in centr. unit)<br />

max<br />

No; IM467 cannot be used<br />

externally together with CP443-5<br />

Number of FMs and CPs that can<br />

be operated (recommendation)<br />

-FM<br />

6ES7 416-2FK02-0AB0<br />

limited by the number of slots and<br />

by the number of connections<br />

- CP, point-to-point limited by the number of slots<br />

- CP, LAN limited and number of<br />

connections<br />

- PROFIBUS and Ether<strong>net</strong> CPs 14; incl. CP 443-5 extended and<br />

IM 467<br />

Time<br />

Clock<br />

- Hardware clock (realtime clock) Yes<br />

- buffered Yes<br />

- Triggering 1 ms<br />

Run-time meter<br />

- Quantity 8<br />

Time synchronization<br />

- supported Yes<br />

- on MPI, master Yes<br />

- on MPI, slave Yes<br />

- on DP, master Yes<br />

- on DP, slave Yes<br />

- in AS, master Yes<br />

- in AS, slave Yes<br />

S7 message functions<br />

• Number of stations that can log on 12<br />

for message functions, max.<br />

• Symbol-related messages Yes<br />

Number of messages<br />

• Block-related messages<br />

Yes<br />

• Alarm 8 blocks<br />

Yes<br />

• Statuses<br />

Yes<br />

Test and startup functions<br />

Status/modify<br />

- Variable Yes<br />

Forcing<br />

- Forcing Yes<br />

• Status block<br />

Yes<br />

• Single step<br />

Yes<br />

• Number of breakpoints 4<br />

Diagnostic buffer<br />

- available Yes<br />

- Number of inputs, max. 3,200<br />

- adjustable Yes<br />

Communication functions<br />

• PG/OP communication<br />

Yes<br />

• Routing<br />

Yes<br />

Global data communication<br />

- supported Yes<br />

- Size of GD packets, max. 64 Byte<br />

S7 basic communication<br />

- supported Yes<br />

- User data per job 76 Byte<br />

S7 communication<br />

- supported Yes<br />

- as server Yes<br />

- as client Yes<br />

- User data per job, max. 64 KByte<br />

5<br />