SIMATIC S7-400<br />
Central processing units<br />
CPU 412-1 to CPU 417-4<br />
■ Technical specifications (continued)<br />
6ES7 412-1XF04-0AB0 6ES7 412-2XG04-0AB0 6ES7 414-2XG04-0AB0 6ES7 414-3XJ04-0AB0<br />
2nd interface<br />
• Physical RS 485 / PROFIBUS RS 485 / PROFIBUS RS 485 / PROFIBUS<br />
• Isolated Yes Yes Yes<br />
Functionality<br />
-DP master Yes Yes Yes<br />
- DP slave Yes Yes Yes<br />
5<br />
DP master<br />
- Number of connections, max. 16 16 16<br />
• Services<br />
- PG/OP communication Yes Yes Yes<br />
- Routing Yes Yes Yes<br />
- S7 basic communication Yes Yes Yes<br />
- S7 communication Yes Yes Yes<br />
- Equidistance support Yes Yes Yes<br />
- Activate/deactivate DP slaves Yes Yes Yes<br />
- Direct data exchange<br />
Yes Yes Yes<br />
(lateral communication)<br />
- Transmission rates, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s<br />
- Number of DP slaves, max. 64 96 96<br />
• Address area<br />
- Inputs, max. 4 KByte 6 KByte 6 KByte<br />
-Outputs, max. 4 KByte 6 KByte 6 KByte<br />
• User data per DP Slave<br />
- Inputs, max. 244 Byte 244 Byte 244 Byte<br />
-Outputs, max. 244 Byte 244 Byte 244 Byte<br />
DP slave<br />
• Services<br />
- Routing Yes Yes Yes<br />
- Status/modify Yes Yes Yes<br />
- Programming Yes Yes Yes<br />
- Transmission rates, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s<br />
• Intermediate memory<br />
- Inputs 244 Byte 244 Byte 244 Byte<br />
-Outputs 244 Byte 244 Byte 244 Byte<br />
- Address areas, max. 32 32 32<br />
- User data per address area,<br />
32 Byte 32 Byte 32 Byte<br />
max.<br />
- User data per address area,<br />
of which consistent, max.<br />
32 Byte 32 Byte 32 Byte<br />
3rd interface<br />
• Type of interface<br />
• Pluggable interface modules<br />
Clock synchronism<br />
• User data per clock<br />
synchronous slave, max.<br />
244 Byte 244 Byte 244 Byte 244 Byte<br />
• Equidistance Yes Yes Yes Yes<br />
• Shortest clock pulse 1 ms 1 ms 1 ms 1 ms<br />
CiR configuration in RUN<br />
• CiR synchronization time,<br />
100 ms 100 ms 100 ms 100 ms<br />
base load<br />
• CiR synchronization time,<br />
time per I/O slave<br />
200 µs 200 µs 80 µs 80 µs<br />
Pluggable interface<br />
module (IF), Technical<br />
specifications as for 2nd<br />
interface<br />
IF 964-DP<br />
5/10 Siemens ST 70 · 2005