SIMATIC S7-<strong>300</strong><br />
Power supplies<br />
Power supplies<br />
■ Technical specifications (continued)<br />
Power supply, type 2 A 2 A 5 A 5 A 10 A<br />
Order No.<br />
6ES7 307-1BA00-<br />
0AA0<br />
6ES7 305-1BA80-<br />
0AA0<br />
6ES7 307-1EA00-<br />
0AA0<br />
6ES7 307-1EA80-<br />
0AA0<br />
6ES7 307-1KA01-<br />
0AA0<br />
SIPLUS Order No.<br />
Output<br />
Stabilized, floating<br />
direct voltage<br />
6AG1 305-1BA80-<br />
2AA0 1)<br />
Stabilized, floating<br />
direct voltage<br />
Stabilized, floating<br />
direct voltage<br />
6AG1 307-1EA80-<br />
2AA0 1)<br />
Stabilized, floating<br />
direct voltage<br />
Stabilized, floating<br />
direct voltage<br />
Rated voltage U e rated 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC<br />
Overall tolerance ± 3 % ± 3 % ± 3 % ± 3 % ± 3 %<br />
• Stat. mains compensation approx. 0.1 % approx. 0.2 % approx. 0.1 % approx. ± 0.2 % approx. ± 0.2 %<br />
• Stat. load compensation approx. 0.2 % approx. 0.4 % approx. 0.2 % approx. ± 0.4 % approx. ± 0.4 %<br />
Residual ripple<br />
(pulse frequency: approx.50kHz)<br />
Spikes (bandwidth: 20 MHz)<br />
< 150 mV pp<br />
(typ. < 20 mV pp )<br />
< 240 mV pp<br />
(typ. < 150 mV pp )<br />
< 150 mV pp<br />
(typ. < 30 mV pp )<br />
< 240 mV pp<br />
(typ. < 150 mV pp )<br />
< 150 mV pp<br />
(typ. 40 mV pp )<br />
< 240 mV pp<br />
(typ. 90 mV pp )<br />
< 150 mV pp<br />
(typ. 40 mV pp )<br />
< 240 mV pp<br />
(typ. 90 mV pp )<br />
< 150 mV pp<br />
(typ. 40 mV pp )<br />
< 240 mV pp<br />
(typ. 90 mV pp )<br />
4<br />
Adjustment range - - - - -<br />
Status display<br />
Green LED for 24 V<br />
O.K.<br />
Green LED for 24 V<br />
O.K.<br />
Green LED for 24 V<br />
O.K.<br />
Green LED for 24 V<br />
O.K.<br />
Green LED for 24 V<br />
O.K.<br />
On/Off response<br />
No overshoot of U a<br />
(soft start)<br />
No overshoot of U a<br />
(soft start)<br />
No overshoot of U a<br />
(soft start)<br />
No overshoot of U a<br />
(soft start)<br />
No overshoot of U a<br />
(soft start)<br />
Startup delay/<br />
voltage rise<br />
< 3 s / typ. 60 ms < 3 s (typ. 7 ms)/<br />
typ. 5 ms<br />
< 2 s (typ. 60 ms) < 3 s/typ. 100 ms < 3 s/typ. 100 ms<br />
Rated current I a rated 2 A 2 A<br />
(3 A at U e > 24 V)<br />
5 A 5 A 5 A<br />
Current range<br />
• Up to +45 °C 0 to 2 A 0 to 2 A (3 A) 0 to 5 A 0 to 5 A 0 to 5 A<br />
• Up to +60 °C 0 to 2 A 0 to 3 A (3 A) 0 to 5 A 0 to 5 A 0 to 5 A<br />
Dyn. U/I at<br />
• Starting on short-circuit typ. 10 A for 90 ms typ. 9 A for 270 ms typ. 20 A for 75 ms typ. 20 A for 180 ms typ. 20 A for 180 ms<br />
• Short-circuit during operation typ. 10 A for 90 ms typ. 9 A for 270 ms typ. 20 A for 75 ms typ. 20 A for 80 ms typ. 20 A for 80 ms<br />
Connection in parallel for increasing<br />
performance<br />
Not permissible Yes, 2 units Not permissible Not permissible Not permissible<br />
Efficiency<br />
Efficiency at U a rated , I a rated approx. 83 % approx. 75% approx. 87 % approx. 84 % approx. 84 %<br />
Power loss at U a rated , I a rated approx. 10 W approx. 16 W (24 W) approx. 18 W approx. 23 W approx. 23 W<br />
Control<br />
Dynamic mains compensation<br />
(U a rated ±15 %)<br />
Dynamic load compensation<br />
(I a : 50/100/50 %)<br />
± 0.3 % U a ± 0.3 % U a ± 0.3 % U a ± 0.3 % U a ± 0.3 % U a<br />
± 0.8 % U a ± 2.5 % U a ± 2.5 % U a ± 3 % U a ± 3 % U a<br />
Load step settling time<br />
• 50 to100 % < 5 ms (typ. 2.5 ms) < 5 ms (typ. 2.5 ms) typ. 0.1 ms < 5 ms (typ. 0.2 ms) < 5 ms (typ. 0.2 ms)<br />
• 100 to 50 % < 5 ms (typ. 2.5 ms) < 5 ms (typ. 2.5 ms) typ. 0.1 ms < 5 ms (typ. 0.2 ms) < 5 ms (typ. 0.2 ms)<br />
Protection and monitoring<br />
Output overvoltage protection<br />
Additional control<br />
loop, shutdown at<br />
approx.30V,<br />
automatic cold<br />
restart<br />
Additional control<br />
loop, shutdown at<br />
approx.30V,<br />
automatic cold<br />
restart<br />
Additional control<br />
loop, shutdown at<br />
approx.30V,<br />
automatic cold<br />
restart<br />
Additional control<br />
loop, shutdown at<br />
approx.30V,<br />
automatic cold<br />
restart<br />
Additional control<br />
loop, shutdown at<br />
approx.30V,<br />
automatic cold<br />
restart<br />
Current limit 2.2 to 2.6 A 3.3 to 3.9 A 5.5 to 6.5 A 5.5 to 6.5 A 5.5 to 6.5 A<br />
Short-circuit protection<br />
Electronic shutdown,<br />
automatic<br />
cold restart<br />
Electronic shutdown,<br />
automatic<br />
cold restart<br />
Electronic shutdown,<br />
automatic<br />
cold restart<br />
Electronic shutdown,<br />
automatic<br />
cold restart<br />
Electronic shutdown,<br />
automatic<br />
cold restart<br />
Continuous r.m.s.<br />
< 4 A < 2 A < 9 A < 5 A < 5 A<br />
short-circuit current<br />
Overload/short-circuit indication - - - - -<br />
1) SIPLUS module for extended temperature range ñ 25 to + 60 ×C and for use under medium loading (e.g. atmospheres containing a high concentration of<br />
chlorine and sulphur ). Currently being prepared for conformity with EN 50155 (for electrical equipment on railway vehicles).<br />
Siemens ST 70 · 2005<br />
4/165