SIMATIC S7-<strong>300</strong><br />

Power supplies<br />

Power supplies<br />

■ Technical specifications (continued)<br />

Power supply, type 2 A 2 A 5 A 5 A 10 A<br />

Order No.<br />

6ES7 307-1BA00-<br />

0AA0<br />

6ES7 305-1BA80-<br />

0AA0<br />

6ES7 307-1EA00-<br />

0AA0<br />

6ES7 307-1EA80-<br />

0AA0<br />

6ES7 307-1KA01-<br />

0AA0<br />

SIPLUS Order No.<br />

Output<br />

Stabilized, floating<br />

direct voltage<br />

6AG1 305-1BA80-<br />

2AA0 1)<br />

Stabilized, floating<br />

direct voltage<br />

Stabilized, floating<br />

direct voltage<br />

6AG1 307-1EA80-<br />

2AA0 1)<br />

Stabilized, floating<br />

direct voltage<br />

Stabilized, floating<br />

direct voltage<br />

Rated voltage U e rated 24 V DC 24 V DC 24 V DC 24 V DC 24 V DC<br />

Overall tolerance ± 3 % ± 3 % ± 3 % ± 3 % ± 3 %<br />

• Stat. mains compensation approx. 0.1 % approx. 0.2 % approx. 0.1 % approx. ± 0.2 % approx. ± 0.2 %<br />

• Stat. load compensation approx. 0.2 % approx. 0.4 % approx. 0.2 % approx. ± 0.4 % approx. ± 0.4 %<br />

Residual ripple<br />

(pulse frequency: approx.50kHz)<br />

Spikes (bandwidth: 20 MHz)<br />

< 150 mV pp<br />

(typ. < 20 mV pp )<br />

< 240 mV pp<br />

(typ. < 150 mV pp )<br />

< 150 mV pp<br />

(typ. < 30 mV pp )<br />

< 240 mV pp<br />

(typ. < 150 mV pp )<br />

< 150 mV pp<br />

(typ. 40 mV pp )<br />

< 240 mV pp<br />

(typ. 90 mV pp )<br />

< 150 mV pp<br />

(typ. 40 mV pp )<br />

< 240 mV pp<br />

(typ. 90 mV pp )<br />

< 150 mV pp<br />

(typ. 40 mV pp )<br />

< 240 mV pp<br />

(typ. 90 mV pp )<br />

4<br />

Adjustment range - - - - -<br />

Status display<br />

Green LED for 24 V<br />

O.K.<br />

Green LED for 24 V<br />

O.K.<br />

Green LED for 24 V<br />

O.K.<br />

Green LED for 24 V<br />

O.K.<br />

Green LED for 24 V<br />

O.K.<br />

On/Off response<br />

No overshoot of U a<br />

(soft start)<br />

No overshoot of U a<br />

(soft start)<br />

No overshoot of U a<br />

(soft start)<br />

No overshoot of U a<br />

(soft start)<br />

No overshoot of U a<br />

(soft start)<br />

Startup delay/<br />

voltage rise<br />

< 3 s / typ. 60 ms < 3 s (typ. 7 ms)/<br />

typ. 5 ms<br />

< 2 s (typ. 60 ms) < 3 s/typ. 100 ms < 3 s/typ. 100 ms<br />

Rated current I a rated 2 A 2 A<br />

(3 A at U e > 24 V)<br />

5 A 5 A 5 A<br />

Current range<br />

• Up to +45 °C 0 to 2 A 0 to 2 A (3 A) 0 to 5 A 0 to 5 A 0 to 5 A<br />

• Up to +60 °C 0 to 2 A 0 to 3 A (3 A) 0 to 5 A 0 to 5 A 0 to 5 A<br />

Dyn. U/I at<br />

• Starting on short-circuit typ. 10 A for 90 ms typ. 9 A for 270 ms typ. 20 A for 75 ms typ. 20 A for 180 ms typ. 20 A for 180 ms<br />

• Short-circuit during operation typ. 10 A for 90 ms typ. 9 A for 270 ms typ. 20 A for 75 ms typ. 20 A for 80 ms typ. 20 A for 80 ms<br />

Connection in parallel for increasing<br />

performance<br />

Not permissible Yes, 2 units Not permissible Not permissible Not permissible<br />

Efficiency<br />

Efficiency at U a rated , I a rated approx. 83 % approx. 75% approx. 87 % approx. 84 % approx. 84 %<br />

Power loss at U a rated , I a rated approx. 10 W approx. 16 W (24 W) approx. 18 W approx. 23 W approx. 23 W<br />

Control<br />

Dynamic mains compensation<br />

(U a rated ±15 %)<br />

Dynamic load compensation<br />

(I a : 50/100/50 %)<br />

± 0.3 % U a ± 0.3 % U a ± 0.3 % U a ± 0.3 % U a ± 0.3 % U a<br />

± 0.8 % U a ± 2.5 % U a ± 2.5 % U a ± 3 % U a ± 3 % U a<br />

Load step settling time<br />

• 50 to100 % < 5 ms (typ. 2.5 ms) < 5 ms (typ. 2.5 ms) typ. 0.1 ms < 5 ms (typ. 0.2 ms) < 5 ms (typ. 0.2 ms)<br />

• 100 to 50 % < 5 ms (typ. 2.5 ms) < 5 ms (typ. 2.5 ms) typ. 0.1 ms < 5 ms (typ. 0.2 ms) < 5 ms (typ. 0.2 ms)<br />

Protection and monitoring<br />

Output overvoltage protection<br />

Additional control<br />

loop, shutdown at<br />

approx.30V,<br />

automatic cold<br />

restart<br />

Additional control<br />

loop, shutdown at<br />

approx.30V,<br />

automatic cold<br />

restart<br />

Additional control<br />

loop, shutdown at<br />

approx.30V,<br />

automatic cold<br />

restart<br />

Additional control<br />

loop, shutdown at<br />

approx.30V,<br />

automatic cold<br />

restart<br />

Additional control<br />

loop, shutdown at<br />

approx.30V,<br />

automatic cold<br />

restart<br />

Current limit 2.2 to 2.6 A 3.3 to 3.9 A 5.5 to 6.5 A 5.5 to 6.5 A 5.5 to 6.5 A<br />

Short-circuit protection<br />

Electronic shutdown,<br />

automatic<br />

cold restart<br />

Electronic shutdown,<br />

automatic<br />

cold restart<br />

Electronic shutdown,<br />

automatic<br />

cold restart<br />

Electronic shutdown,<br />

automatic<br />

cold restart<br />

Electronic shutdown,<br />

automatic<br />

cold restart<br />

Continuous r.m.s.<br />

< 4 A < 2 A < 9 A < 5 A < 5 A<br />

short-circuit current<br />

Overload/short-circuit indication - - - - -<br />

1) SIPLUS module for extended temperature range ñ 25 to + 60 ×C and for use under medium loading (e.g. atmospheres containing a high concentration of<br />

chlorine and sulphur ). Currently being prepared for conformity with EN 50155 (for electrical equipment on railway vehicles).<br />