SIMATIC S7-<strong>300</strong><br />

Central processing units<br />

CPU 312C to CPU 317F-2 DP<br />

■ Technical specifications (continued)<br />

4<br />

6ES7 312-1AD10-<br />

0AB0<br />

6ES7 314-1AF10-<br />

0AB0<br />

6ES7 315-2AG10-<br />

0AB0<br />

6ES7 317-2AJ10-<br />

0AB0<br />

6ES7 318-2AJ00-<br />

0AB0<br />

Time<br />

Clock<br />

- Hardware clock (realtime clock) Yes Yes Yes Yes<br />

- Software clock Yes<br />

- buffered No Yes Yes Yes Yes<br />

- Deviation per day, max 15 s 10 s 10 s 10 s 10 s<br />

Run-time meter<br />

- Quantity 1 1 1 4 8<br />

-Number 0 0 0 0 to 3 0 to 7<br />

- Range of values 0 to 2 31 hours (when 0 to 2 31 hours (when 0 to 2 31 hours (when 0 to 2 31 hours (when 0 to 32767 hours<br />

using SFC 101) using SFC 101) using SFC 101) using SFC 101)<br />

- Granularity 1 hour 1 hour 1 hour 1 hour 1 hour<br />

- retentive Yes; must be<br />

restarted on each<br />

complete restart<br />

Yes; must be<br />

restarted on each<br />

complete restart<br />

Yes; must be<br />

restarted on each<br />

complete restart<br />

Yes; must be<br />

restarted on each<br />

complete restart<br />

Time synchronization<br />

- supported Yes Yes Yes Yes Yes<br />

- on MPI, master Yes Yes Yes Yes Yes<br />

- on MPI, slave Yes Yes Yes Yes Yes<br />

- in AS, master Yes Yes Yes Yes Yes<br />

- in AS, slave Yes Yes<br />

S7 message functions<br />

• Number of stations that can log on<br />

for message functions, max.<br />

6; depending on the<br />

connections configured<br />

for PG/OP and<br />

S7 basic communication<br />

12; depending on<br />

the connections<br />

configured for<br />

PG/OP and S7<br />

basic communication<br />

16; depending on<br />

the connections<br />

configured for<br />

PG/OP and S7<br />

basic communication<br />

32; depending on<br />

the connections<br />

configured for<br />

PG/OP and S7<br />

basic communication<br />

• Process diagnostic messages Yes Yes Yes Yes Yes<br />

• simultaneously active Alarm-S 20 40 40 60 100<br />

blocks, max.<br />

Test and startup functions<br />

Status/modify<br />

- Variable Yes Yes Yes Yes Yes<br />

-Variables<br />

Inputs, outputs,<br />

flags, DB, timers,<br />

counters<br />

Inputs, outputs,<br />

flags, DB, timers,<br />

counters<br />

Inputs, outputs,<br />

flags, DB, timers,<br />

counters<br />

Inputs, outputs,<br />

flags, DB, timers,<br />

counters<br />

Inputs, outputs,<br />

flags, DB, timers,<br />

counters<br />

- Number of variables, max. 30 30 30 30 70<br />

- of which status variables, max. 30 30 30 30<br />

- of which modify variables, max. 14 14 40 14<br />

Forcing<br />

- Forcing Yes Yes Yes Yes Yes<br />

- Forcing, variables Inputs,<br />

outputs<br />

Inputs,<br />

outputs<br />

Inputs,<br />

outputs<br />

Inputs,<br />

outputs<br />

- Forcing, number of variables, 10 10 10 10 256<br />

max.<br />

• Status block Yes Yes Yes Yes Yes<br />

• Single step Yes Yes Yes Yes Yes<br />

• Number of breakpoints 2 2 2 2 4<br />

Diagnostic buffer<br />

- available Yes Yes Yes Yes Yes<br />

- Number of inputs, max. 100 100 200 100 100<br />

- adjustable No No No No No<br />

Yes<br />

Inputs, outputs,<br />

memory markers,<br />

distributed inputs,<br />

distributed outputs<br />

4/22 Siemens ST 70 · 2005