SIMATIC S7-<strong>300</strong><br />

Function modules<br />

SM 338 ultrasonic position encoder<br />

■ Overview<br />

■ Technical specifications<br />

4<br />

An ultrasonic measuring system comprises:<br />

• SIMATIC S7-<strong>300</strong> with CPU and power supply<br />

• The SM 338 ultrasonic position decoding module<br />

• 24 V external supply voltage<br />

• Ultrasonic position sensor(s)<br />

Ultrasonic position sensors with the following characteristics can<br />

be used:<br />

• START/STOP interface with RS 422 signals<br />

• One power supply for all sensors that are simultaneously<br />

connected to the SM 338 module: +/- 15 V / max. 200 mA<br />

floating or +24 V / max. <strong>300</strong> mA floating.<br />

For a sensor length of less than 3 m, the resolution is 0.05 mm.<br />

At the maximum sensor length of 6 m, the resolution is 0.1 mm.<br />

With more than one measuring point on a sensor, the sensorspecific<br />

minimum spacing must be complied with. This ensures<br />

that there is no mutual interference between the measuring<br />

points.<br />

Position sensors<br />

Number up to 4<br />

Max no. of measuring points 8, up to 4 per sensor<br />

Measuring range<br />

3 m and 6 m<br />

Resolution<br />

0.05 mm (up to 3 m measuring<br />

range) and 0.1 mm<br />

Programmable measuring cycle 0.5 ms ... 16 ms<br />

Supply voltage for sensors<br />

• With galvanic isolation<br />

-Voltage<br />

±15 V<br />

- Current 200 mA<br />

• Without galvanic isolation<br />

-Voltage<br />

24 V DC<br />

- Current, total <strong>300</strong> mA, without galvanic isolation<br />

Total power for supplying<br />

7.2 W<br />

the sensors max.<br />

Supply voltage for the module<br />

Current consumption<br />

• Internal from S7-<strong>300</strong><br />

typ. 80 mA; max. 1000 mA<br />

backplane bus<br />

• External voltage<br />

20.4 V ... 28.8 V<br />

• Without sensors max.<br />

0.1 A<br />

• With sensors max.<br />

0.85 A<br />

Fuse<br />

1.0 A slow-acting<br />

Polarity reversal protection<br />

Yes<br />

Operating conditions<br />

Ambient temperature<br />

• Horizontal mounting position 0 °C ... +60 °C<br />

• for vertical installation 0 °C ... +40 °C<br />

Relative air humidity<br />

5 ... 95% (without condensation)<br />

Atmospheric pressure<br />

860 hPa ... 1080 hPa<br />

Pollutant concentration<br />

•SO 2 max.<br />

10 ppm<br />

•H 2 S max.<br />

1ppm<br />

Vibration<br />

• 10 Hz ... 57 Hz<br />

0.075 mm amplitude<br />

• 57 Hz ... 150 Hz<br />

1 g constant acceleration<br />

Conditons for storage and transport (in original packaging)<br />

Free fall (to IEC 1131-2)