SIMATIC S7-<strong>300</strong><br />
Function modules<br />
SM 338 ultrasonic position encoder<br />
■ Overview<br />
■ Technical specifications<br />
4<br />
An ultrasonic measuring system comprises:<br />
• SIMATIC S7-<strong>300</strong> with CPU and power supply<br />
• The SM 338 ultrasonic position decoding module<br />
• 24 V external supply voltage<br />
• Ultrasonic position sensor(s)<br />
Ultrasonic position sensors with the following characteristics can<br />
be used:<br />
• START/STOP interface with RS 422 signals<br />
• One power supply for all sensors that are simultaneously<br />
connected to the SM 338 module: +/- 15 V / max. 200 mA<br />
floating or +24 V / max. <strong>300</strong> mA floating.<br />
For a sensor length of less than 3 m, the resolution is 0.05 mm.<br />
At the maximum sensor length of 6 m, the resolution is 0.1 mm.<br />
With more than one measuring point on a sensor, the sensorspecific<br />
minimum spacing must be complied with. This ensures<br />
that there is no mutual interference between the measuring<br />
points.<br />
Position sensors<br />
Number up to 4<br />
Max no. of measuring points 8, up to 4 per sensor<br />
Measuring range<br />
3 m and 6 m<br />
Resolution<br />
0.05 mm (up to 3 m measuring<br />
range) and 0.1 mm<br />
Programmable measuring cycle 0.5 ms ... 16 ms<br />
Supply voltage for sensors<br />
• With galvanic isolation<br />
-Voltage<br />
±15 V<br />
- Current 200 mA<br />
• Without galvanic isolation<br />
-Voltage<br />
24 V DC<br />
- Current, total <strong>300</strong> mA, without galvanic isolation<br />
Total power for supplying<br />
7.2 W<br />
the sensors max.<br />
Supply voltage for the module<br />
Current consumption<br />
• Internal from S7-<strong>300</strong><br />
typ. 80 mA; max. 1000 mA<br />
backplane bus<br />
• External voltage<br />
20.4 V ... 28.8 V<br />
• Without sensors max.<br />
0.1 A<br />
• With sensors max.<br />
0.85 A<br />
Fuse<br />
1.0 A slow-acting<br />
Polarity reversal protection<br />
Yes<br />
Operating conditions<br />
Ambient temperature<br />
• Horizontal mounting position 0 °C ... +60 °C<br />
• for vertical installation 0 °C ... +40 °C<br />
Relative air humidity<br />
5 ... 95% (without condensation)<br />
Atmospheric pressure<br />
860 hPa ... 1080 hPa<br />
Pollutant concentration<br />
•SO 2 max.<br />
10 ppm<br />
•H 2 S max.<br />
1ppm<br />
Vibration<br />
• 10 Hz ... 57 Hz<br />
0.075 mm amplitude<br />
• 57 Hz ... 150 Hz<br />
1 g constant acceleration<br />
Conditons for storage and transport (in original packaging)<br />
Free fall (to IEC 1131-2)