■ Technical specifications (continued)<br />
6ES7 355-<br />
0VH10-0AE0<br />
6ES7 355-<br />
1VH10-0AE0<br />
Analog inputs<br />
• Number of analog inputs 4 4<br />
• Length of cable shielded, max 200 m; 50m at<br />
80 mV and<br />
thermocouples<br />
200 m; 50m at<br />
80 mV and<br />
thermocouples<br />
• Permissible input voltage for the 30 V 30 V<br />
voltage input (destruction limit),<br />
max.<br />
• Permissible input voltage for the 40 mA 40 mA<br />
current input (destruction limit),<br />
max.<br />
Input ranges (rated values),<br />
voltages<br />
- 0 to +10 V Yes Yes<br />
- -1.75 to +11.75 V Yes Yes<br />
- -80 mV to +80 mV Yes Yes<br />
Input ranges (rated values),<br />
currents<br />
- 0 to 20 mA Yes Yes<br />
- 0 to 23.5 mA Yes Yes<br />
- -3.5 to +23.5 mA Yes Yes<br />
- 4 to 20 mA Yes Yes<br />
Input ranges (rated values),<br />
thermocouples<br />
- Type B Yes Yes<br />
- Type J Yes Yes<br />
- Type K Yes Yes<br />
- Type R Yes Yes<br />
- Type S Yes Yes<br />
Input ranges (rated values),<br />
resistance thermometer<br />
- Pt 100 Yes Yes<br />
Characteristic curve linearization<br />
- parameterizable Yes Yes<br />
- for thermocouples Typ B, J, K, R, S Typ B, J, K, R, S<br />
- for resistance thermometer Pt 100<br />
(Standard)<br />
Temperature compensation<br />
- external temperature<br />
Yes<br />
compensation with Pt100<br />
- internal temperature<br />
Yes<br />
compensation possible<br />
Analog outputs<br />
• Number of analog outputs 4<br />
• Length of cable shielded, max 200 m;<br />
50m at 80 mV<br />
and thermocouples<br />
• Voltage output, short-circuit Yes<br />
protection<br />
• Voltage output, short-circuit 25 mA<br />
current, max<br />
• Current output, open-circuit 18 V<br />
voltage, max.<br />
Pt 100<br />
(Standard)<br />
Yes<br />
Yes<br />
SIMATIC S7-<strong>300</strong><br />
Function modules<br />
FM 355 closed-loop control modules<br />
6ES7 355-<br />
0VH10-0AE0<br />
6ES7 355-<br />
1VH10-0AE0<br />
Analog outputs (continued)<br />
Output ranges, voltage<br />
- 0 to 10 V Yes<br />
- -10 to +10 V Yes<br />
Output ranges, current<br />
- 0 to 20 mA Yes<br />
- 4 to 20 mA Yes<br />
Actuator connection<br />
- for voltage output 2-wire<br />
connection<br />
Yes<br />
- for current output 2-wire<br />
connection<br />
Yes<br />
Burden resistance<br />
(in the nominal output range)<br />
- at voltage outputs, min. 1 kΩ<br />
- at voltage outputs, capacitive 1 µF<br />
load, max.<br />
- at current outputs, max. 500 Ω<br />
- at current outputs, inductive 1 mH<br />
load, max.<br />
Analog value formation<br />
• Measuring principle integrating integrating<br />
Integration and conversion<br />
time/triggering per channel<br />
- with over-range (bits incl. sign),<br />
max.<br />
14 Bit;<br />
12 or 14 bits,<br />
parameterizable<br />
- Conversion time (per channel) 16.67 ms;<br />
at 12 bits:<br />
16 2/3 ms<br />
at 60 Hz,<br />
20 ms<br />
at 50 Hz;<br />
at 14 bits:<br />
100 ms<br />
at 50 and 60 Hz<br />
14 Bit;<br />
12 or 14 bits,<br />
parameterizable<br />
16.67 ms;<br />
at 12 bits:<br />
16 2/3 ms<br />
at 60 Hz,<br />
20 ms<br />
at 50 Hz;<br />
at 14 bits:<br />
100 ms<br />
at 50 and 60 Hz<br />
Settling time<br />
- for resistive load 0.1 ms 0.1 ms<br />
- for capacitive load 3.3 ms 3.3 ms<br />
- for inductive load 0.5 ms 0.5 ms<br />
Sensor<br />
Sensing element connection<br />
- for voltage measurement Yes Yes<br />
- for current measurement, Yes<br />
Yes<br />
as 4-wire measuring transducer<br />
Connectable encoders<br />
- 2-wire BEROS Yes Yes<br />
- permissible closed-circuit<br />
current (2-wire BEROS), max.<br />
1.5 mA 1.5 mA<br />
4<br />
Siemens ST 70 · 2005<br />