simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
simatic s7-300 - megaelektrik.net
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4<br />
SIMATIC S7-<strong>300</strong><br />
Function modules<br />
FM 355 closed-loop control modules<br />
■ Overview<br />
• 4-channel closed-loop control module for universal closedloop<br />
control tasks<br />
• Used for temperature, pressure, flowrate and fill-level control<br />
loops<br />
• User-friendly online self-optim ization for temperature controls<br />
• Preprogrammed controller structures<br />
• 2 control algorithms<br />
• 2 versions:<br />
- FM 355 C as continuous-action controller;<br />
- FM 355 S as step or pulse controller<br />
• With 4 analog outputs (FM 355 C) or 8 digital outputs (FM 355 S)<br />
for direct control of the most common types of actuator<br />
• Continued operation of the contro l loop is possible even after<br />
a CPU stop or failure<br />
■ Technical specifications<br />
6ES7 355-<br />
0VH10-0AE0<br />
6ES7 355-<br />
1VH10-0AE0<br />
Voltages and currents<br />
Load voltage L+<br />
- Rated value (DC) 24 V 24 V<br />
- permissible range,<br />
20.4 V 20.4 V<br />
lower limit (DC)<br />
- permissible range,<br />
upper limit (DC)<br />
28.8 V 28.8 V<br />
Current consumption<br />
• from load voltage L+ (no load),<br />
max.<br />
• from backplane bus 5 V DC, max.<br />
310 mA;<br />
typ. 260 mA<br />
75 mA;<br />
typ. 50 mA<br />
270 mA;<br />
typ. 220 mA<br />
75 mA;<br />
typ. 50 mA<br />
• Power dissipation, max. 7.8 W 6.9 W<br />
• Power dissipation, typical 6.5 W 5.5 W<br />
Connection system<br />
• Requisite front connector 2 x 20-pin 2 x 20-pin<br />
Digital inputs<br />
• Number of digital inputs 8 8<br />
Length of cable<br />
- Length of cable shielded, max. 1,000 m 1,000 m<br />
- Length of cable unshielded, 600 m 600 m<br />
max.<br />
• Input characteristic to comply with Yes<br />
Yes<br />
IEC 1131, Type 2<br />
Input voltage<br />
- Rated value, DC 24 V 24 V<br />
- for signal "0" -3 to 5 V -3 to 5 V<br />
- for signal "1" 13 to 30 V 13 to 30 V<br />
Input current<br />
- for 1 signal, typical 7 mA 7 mA<br />
6ES7 355-<br />
0VH10-0AE0<br />
6ES7 355-<br />
1VH10-0AE0<br />
Digital outputs<br />
• Number of digital outputs 8<br />
• Length of cable shielded, max.<br />
1,000 m<br />
• Length of cable unshielded, max.<br />
600 m<br />
• Short-circuit protection of the<br />
output<br />
• Limitation of voltage induced on<br />
circuit interruption to<br />
• Lamp load, max.<br />
• Driving a digital input<br />
Yes;<br />
electronic<br />
L+ (-1.5 V)<br />
5 W<br />
Yes<br />
Output voltage<br />
- for 1 signal L+ (-2.5 V)<br />
Output current<br />
- for 1 signal rated value 100 mA<br />
- for 1 signal permissible range<br />
for 0 to 60 °C, min.<br />
5 mA<br />
- for 1 signal permissible range<br />
for 0 to 60 °C, max.<br />
150 mA<br />
- for 0 signal residual current, max. 0.5 mA<br />
Parallel switching of 2 outputs<br />
- for logical links Yes<br />
Switching frequency<br />
- at resistive load, max. 100 Hz<br />
- at inductive load, max. 0.5 Hz<br />
- at lamp load, max. 100 Hz<br />
Summation current of the outputs<br />
(per group)<br />
- up to 60 °C, max. 400 mA<br />
Load impedance range<br />
- lower limit 240 Ω<br />
- upper limit 4 kΩ<br />