RATIOMETRIC<br />

V-Notch Angle Weir (Non BS 3680)<br />

If the flow calculation is to be ratiometric P702 = 2 the flow will be<br />

calculated using the formula: q= q cal (h+kh/h cal +kh) 2.5<br />

Where: q = flowrate<br />

q cal = flowrate at maximum head P705<br />

h = head<br />

kh = compensated head<br />

Universal Calculations (P700 = 6)<br />

Point of Measurement<br />

The transducer must be above the maximum head P704 by at least the near<br />

blanking distance P107.<br />

For all Universal calculation applications the point at which the head is<br />

measured should be chosen such that the surface of the liquid is not effected<br />

by turbulence.<br />

Calculations<br />

ABSOLUTE<br />

Universal Head Vs Flow<br />

If the flow calculation is to be absolute P702 = 1 the flow will be calculated<br />

using the formula: q = q(h)<br />

Where: q = flowrate<br />

q(h) = flowrate for head<br />

The desired number of Breakpoints, (P730 - P793) are to be entered in<br />

pairs in values of head and corresponding flow. (Minimum of 2 pairs of<br />

Breakpoints is required).<br />