To program the <strong>FlowCERT</strong> for Example 1 V-Notch Weir by using the<br />

Quick Setup menu proceed as follows.<br />

If required access the Program Mode<br />

Key in the passcode 1997 and press ENTER<br />

Using the ‘right’ arrow key go to the Quick Setup menu press ENTER and<br />

as prompted, by the questions, select the relevant option and press ENTER.<br />

Question<br />

Option<br />

PMD Type 1 = Exponent<br />

Exponent<br />

6 = V notch.<br />

Calculation 2 = Ratiometric.<br />

No. of Alarms 0 = No Alarms<br />

Xducer<br />

9 = DUET<br />

Volume Units 1 = Litres<br />

Time Units 1 = Per Second<br />

Measnt. Units 1 = metres<br />

Empty Level 1.000 metres<br />

Minimum Head 0.000 metres<br />

Maximum Head 0.400 metres<br />

Total Enable 1 = On<br />

Totaliser ( R ) 0 = No<br />

Total Multiplier 7 = 1000<br />

Maximum Flow 96.5<br />

Programming is now complete and the unit can now be returned to the run<br />

mode, press CANCEL until Run Mode? Is displayed on the LCD press<br />

ENTER, and the <strong>FlowCERT</strong> will return to Run Mode.<br />

Page 58