Parameter Default Description<br />

P101<br />

9 = DUET Type of Transducer to be used.<br />

Transducer<br />

P706<br />

Volume Units<br />

1 = Litres Units of flow as on display and used<br />

P707<br />

Time Units<br />

P104<br />

Measnt Units<br />

P105<br />

Empty Level<br />

P703<br />

Minimum<br />

Head<br />

P704<br />

Max Head<br />

P824<br />

Totaliser<br />

Enable<br />

P816<br />

Totaliser ( R )<br />

for calculations.<br />

1=litres<br />

3=cubic feet<br />

5=US gallons<br />

2 = cubic metres<br />

4 = UK gallons<br />

6 = Mil.USG<br />

1 = per second Units of time that volume units will<br />

be displayed and calculated in.<br />

1= units/sec. 2= units/min.<br />

3= units/hour 4= units/day<br />

1 = metres Units used to enter dimensions, and<br />

displayed where appropriate.<br />

1 = metres 2 = centimetres<br />

3 = millimetres 4 = feet<br />

5 = inches<br />

2.000 m Distance from the face of the<br />

transducer (lower transducer on<br />

DUET) or the end of transducer horn<br />

(dB Mach 3), to the material at the<br />

bottom of the measuring element.<br />

0.000m Distance from empty point (P105) to<br />

zero flow.<br />

1.700m Distance from zero flow to max<br />

flow. It should be noted that any<br />

change to P704 updates P106 Span<br />

and vice versa.<br />

1=On Enables the flow totaliser, P820,<br />

options are 0=Off, 1=On. Note this<br />

totaliser can be viewed during run<br />

via the totaliser “Hot Key” It can be<br />

reset but only via P820, whilst in<br />

“program mode”.<br />

0=No<br />

Enables the totaliser to be displayed<br />

in the auxiliary display whilst in “run<br />

mode”. Note this totaliser is<br />

“resettable”, whilst in “run mode”,<br />

via the totaliser hot key.<br />

Page 49