Velocity (current)<br />

Parameter Details<br />

Entered Values<br />

No. Description Default 1 2 3 4 5<br />

P726 Low mA In 4.0 mA<br />

P727 High mA In 20.0 mA<br />

P728 Low Vel. In 0.000 m/s<br />

P729 High Vel. In 3.000 m/s<br />

Velocity (Speedy)<br />

Parameter Details<br />

Entered Values<br />

No. Description Default 1 2 3 4 5<br />

P680 Speedy Update Interval 0 seconds<br />

P681 Sound Velocity in Water 1450m/sec.<br />

P682 Minimum Flow Velocity -4.00m/sec.<br />

P683 Maximum Flow Velocity 6.00m/sec.<br />

P684 Damping Factor 5 sec.<br />

P685 Peak Width 20%<br />

P686 Minimum Signal Quality 35%<br />

P687 Stability 20secs<br />

P688 Gain 30dB<br />

P689 Speedy Level 0.30m<br />

P690 Automatic Gain Control 1 (Yes)<br />

P691 High Level Trigger 1 (Yes)<br />

DISPLAY<br />

Options<br />

Parameter Details<br />

Entered Values<br />

No. Description Default 1 2 3 4 5<br />

P800 Display Units 1 = measured<br />

P801 Decimal Places 2<br />

P802 Display Offset 0.000 metres<br />

P804 Display Conversion 1.000<br />

Fail Safe<br />

Parameter Details<br />

Entered Values<br />

No. Description Default 1 2 3 4 5<br />

P808 Fail Mode 1 = Known<br />

P809 Fail Time 2.0 mins<br />

Page 162