Example<br />
Telephone number to be dialled is: 0 1234 123456<br />
P145 Tel. No. 1 = 1 (One ‘0’ at the beginning of the telephone number)<br />
P146 Tel. No. 2 = 123412 (The next 6 digits following the ‘0’s).<br />
P147 Tel. No. 3 = 3456 (Remaining digits of telephone number).<br />
P148 Timed Out<br />
This parameter will set the time period that the unit will wait for a reply<br />
before disconnecting. Default = 90 seconds<br />
P149 Retry No.<br />
This parameter will set the number of times the telephone number will be redialled<br />
if no reply is received. If set to ‘0’ then the number will be re-dialled<br />
continually until a reply is received, if set to ‘-1’ then the number will not be<br />
re-dialled at all. Any other value entered between 1 and 99 will determine<br />
the number of re-dials to be attempted. Default = 0<br />
Test Parameters<br />
Simulation<br />
P980 Simulate<br />
Test mode is used to simulate the application and confirm that all<br />
parameters and relay setpoints have been entered as expected. During<br />
simulation, there is a choice of whether the relays will change state (hard<br />
simulation) or not (soft simulation), but the LED’s will always change<br />
colour as programmed, and the current output will change. If you want to<br />
test the logic of the system that the relays are connected to then select a hard<br />
simulation, but if you don’t want to change the relay state, then select a soft<br />
simulation.<br />
There are two simulation modes, automatic and manual. Automatic<br />
simulation will move the level up and down between empty level or the predetermined<br />
Start Level (P983) and Pump/Control relay switch points, if<br />
you wish to change the direction of the level movement e.g. to go beyond<br />
relay setpoints, this can be done by using the arrow keys. In manual<br />
simulation, using the arrow keys will allow you to move the level up and<br />
down as required.<br />
Page 148