07.09.2015 Views

FlowCERT

Flow Cert Second Edition.pdf - Pulsar Process Measurement

Flow Cert Second Edition.pdf - Pulsar Process Measurement

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

P884 Peak Percent<br />

This parameter is used if you choose a solids application, P102 Material =<br />

2 (Solids), where there maybe angles of repose on the material, and can be<br />

used to determine where in the returned echo the displayed level is.<br />

Default = 50%<br />

Echo Processing Parameters<br />

Transducer 1 Status<br />

P900 Transducer 1 Status<br />

This parameter shows the current state of the transducer. The value means<br />

the following.<br />

Option<br />

Description<br />

0= OK Transducer working correctly.<br />

1= Disabled Transducer is not being used (mA input is being<br />

used instead, so P101=1)<br />

2= Stuck High Indicates that the power and signal lines on the<br />

transducer terminals are crossed over, or the signal<br />

line is shorted to earth.<br />

3= Not Found No transducer is detected.<br />

P901 Echo Confidence1<br />

This parameter displays the most recent echo confidence from the<br />

transducer. It is useful to help find the best mounting location for the<br />

transducer, where you should aim to get the highest figure. It is a percentage<br />

of confidence that the echo reporting the level is the correct one.<br />

P902 Echo Strength1<br />

This parameter displays the most recent echo strength figure for the<br />

transducer, where a higher figure indicates a better returned echo.<br />

P903 Average Noise1<br />

This is the mean noise reading for the transducer. It is measured while the<br />

transducer is not firing, and gives an indication of the average amount of<br />

electrical noise present on the cabling.<br />

P904 Peak Noise1<br />

This is the peak noise reading for the transducer. It is measured while the<br />

transducer is not firing, and gives an indication of the maximum amount of<br />

electrical noise present on the cabling.<br />