P876 Rate Distance<br />
This parameter is the rate Measurement Units (P104) over which the<br />
material level must change before the Rate Value (P877) is updated. If the<br />
Rate Time (P875) expires before the Rate Distance (P876) is exceeded<br />
then the Rate Value (P877) will be updated immediately. Default = 0.05m<br />
P877 Rate Value<br />
This parameter displays the current rate of change of material level, in<br />
Measurement Units (P104) per minute. It is read only.<br />
P878 Lower Cutoff<br />
This parameter is used to select the minimum Rate to be calculated, and can<br />
be used to eliminate unwanted updates from effects of ripples/waves on the<br />
surface of the material.<br />
Filters<br />
The following three parameters can be used to filter out unwanted changes<br />
of level caused by a ‘rippled’ or agitated surface.<br />
P880 Gate Mode<br />
This parameter determines the operation of the gate, which is established<br />
around the processed echo and is used to track the echoes movement and<br />
update the display. If set to Fixed, P880 = 0 (Default) then the width of the<br />
gate is determined by the value of P881 Fixed Distance. When set to<br />
Calculated, P880=1 then the gate width is automatically calculated and<br />
updated according to the values of P870, P871, P874, P875 and P876.<br />
P881 Fixed Distance<br />
This parameter determines the width of gate to be used in tracking an echo<br />
and under normal circumstances will not require changing, but it can be<br />
increased in the cases where the surface is moving extremely fast (in excess<br />
of 10m/min) to ensure smooth processing of the changing level.<br />
P882 Process Filter<br />
This parameter determines the number of ‘cycles’ that will be taken before a<br />
change in level is processed and the display updated.<br />
Option<br />
Description<br />
1 = Fast level will be updated every cycle<br />
2 = Medium level will be updated every 8 cycles<br />
3 = Slow (Default) level will be updated every 16 cycles<br />