Average Flow<br />

P863 Average Flow<br />

This parameter will display the Average Flow for the time period set in<br />

Average Time (P864). It is read only and cannot be changed.<br />

P864 Average Time<br />

This parameter will set the time period over which the Average Flow (P863)<br />

is to be calculated before being displayed.<br />

Display Parameters<br />

Options<br />

P800 Display Units<br />

This parameter determines whether the reading displayed is in<br />

Measurement Units (P104), or as a percentage of span.<br />

Option<br />

Description<br />

1 = Measured (Default) Display is in selected units dependant in<br />

Mode (P100)<br />

2 = Percentage Display is in percentage of span<br />

dependant in Mode (P100).<br />

P801 Decimal Places<br />

This parameter determines the number of decimal places on the reading<br />

during run mode.<br />

Minimum = 0 (No decimal places), Maximum 3 = (3 decimal Places)<br />

Default = 2 (2 decimal Places)<br />

P802 Display Offset<br />

The value of this parameter is added to the reading before it is displayed, in<br />

Measurement Units (P104).<br />

It does not affect the relay setpoints or the mA output, only the reading on<br />

the display.<br />

You could use this feature if for example you wanted to reference the<br />

reading to sea level, where you would enter the distance between Empty<br />

Level (P105) and sea level. If the empty level point is below sea level, then<br />

enter a negative value.<br />

Page 123