Velocity<br />
The calculation of flow using Velocity Area is only possible when the<br />
current input or “speedy” velocity sensor is used to provide an input signal<br />
proportional to the velocity of the flow.<br />
When P130 Device Mode = 0 Off or 1 Modbus, using current input<br />
Parameters P726 to P729 are used to configure the optional 4 -20mA input<br />
for a velocity sensing device. When an Area/Velocity application is selected<br />
the unit will automatically allocate the 4-20mA input to a velocity input<br />
device and it is therefore not necessary to allocate P101 Transducer = 0<br />
(Auxiliary).<br />
P726 Low mA In<br />
This parameter sets the mA current input figure that is used to represent<br />
minimum velocity (P728) when the current input is allocated to a velocity<br />
input device. Default = 4 mA<br />
P727 High mA In<br />
This parameter sets the mA current input figure that is used to represent<br />
maximum velocity (P729) when the current input is allocated to a velocity<br />
input device. Default = 20 mA<br />
P728 Low Vel. In<br />
This parameter sets the minimum velocity, at low mA In (P726) when the<br />
current input is allocated to a velocity input device. Default = 0 m/sec<br />
P729 High Vel. In<br />
This parameter sets the maximum velocity, at High mA In (P727) when the<br />
current input is allocated to a velocity input device. Default = 3 m/sec<br />
Page 119