P717 Exponent<br />
This parameter is used to enter the exponent value when:<br />
P700 PMD Type = 1 Exponent and P701 Primary M.D = 7 Others.<br />
P718 K Factor<br />
This parameter is used to enter the K Factor when:<br />
P700 PMD Type = 1 Exponent and P702 Calculation = 1 Absolute see table<br />
below for further details.<br />
Primary Measuring Device P718 K<br />
Factor<br />
P700 = 1 Exponent<br />
P701 = 1 Supp. Rectangular Weir<br />
Automatically<br />
Calculated<br />
P700 = 1 Exponent<br />
P701 = 2 Trapezod Weir<br />
Automatically<br />
Calculated<br />
P700 = 1 Exponent<br />
P701 = 3 Venturi Flume<br />
Obtain value<br />
and enter<br />
P700 = 1 Exponent<br />
P701 = 4 Parshall Flume<br />
Automatically<br />
Calculated<br />
P700 = 1 Exponent<br />
P701 = 5 Leopald Lagco Flume<br />
Automatically<br />
Calculated<br />
P700 = 1 Exponent<br />
P701 = 6 V Notch<br />
Automatically<br />
Calculated<br />
P700 = 1 Exponent<br />
P701 = 7 Other<br />
Obtain value<br />
and enter<br />
P719 Throat Width<br />
This parameter is used to select the Throat Width of the flume when:<br />
P700 PMD Type = 1 Exponent and P701 = 4 Parshall Flume. After selecting<br />
the Throat Width the Exponent P717 and K Factor P 718 will be set<br />
automatically.<br />
Page 117