Important Information<br />

When using a Relay to control a device at a specified time of day ensure that<br />

the Time P932 is set correctly. And if required, enable Daylight Saving for<br />

the appropriate time difference P970 – P979.<br />

Page 106<br />

The third parameter has no function when miscellaneous relay is chosen<br />

and will not be displayed.<br />

The fourth parameter, and fifth parameter, are set to determine the switch<br />

points, “ON” and “OFF” for the relay. See miscellaneous function table<br />

(P211, 221, 231, 241, 251) for further information.<br />

P211, 221, 231, 241, 251 = 1 (Clock)<br />

P213, P223, P233, P243, P253 - Relay Setpoint 1<br />

Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which<br />

relay will energise. Default = 00:00 (HH:MM)<br />

P214, P224, P234, P244, P254 - Relay Setpoint 2<br />

Relay Setpoints are entered in Minutes to set Time Period that the relay will<br />

remain ON. Default = 0.00 mins.<br />

P211, 221, 231, 241, 251 = 2 (Totaliser)<br />

P213, P223, P233, P243, P253 - Relay Setpoint 1<br />

Relay Setpoints are entered as a factor by which the on board totaliser (P820)<br />

should be multiplied by to provide a relay closure. Default = 0.00<br />

P214), P224, P234, P244, P254 - Relay Setpoint 2<br />

Relay Setpoints are entered in seconds to set the time period that the relay will<br />

remain ‘ON’. Default = 0.00 secs.<br />

P219, P229, P239, P249, P259 - Relay Max.Rate<br />

This parameter will allow a pump to be switched at a pre-determined Rate<br />

of change of Level, irrespective of the “ON” level setpoint P213, 223, 233,<br />

243, 253. Once a General Control relay has been switched “ON” by the predetermined<br />

Rate of Change, it will remain energised until the level reaches<br />

the “OFF” level setpoint P214, 224, 234, 244, 254.<br />

Max. Rate is entered in Measurement Units (P104) per minute and can be<br />

entered as either positive (increasing level) or negative (decreasing level)<br />

values.