The third parameter for each relay determines the assignment or<br />

condition of the relay, where required.<br />

P212, P222, P232, P242, P252 - Relay Alarm ID/Pump Group,<br />

P211, 221, 231, 241, 251 = 2 (Step Time)<br />

If the relay is selected for Step Time, then this parameter is used to assign<br />

the relay to the 0 = Open condition (increase level) or 1 = Close condition<br />

(decrease level).<br />

The fourth parameter, fifth parameter and sixth parameter are set to<br />

determine the switch points, “ON” and “OFF” for the relay and where<br />

required the order of start. See control function, table (P211, 221, 231, 241,<br />

251) for further information.<br />

P213, P223, P233, P243, P253 Relay Setpoint 1<br />

P211, 221, 231, 241, 251 =1 (Time)<br />

This parameter determines the “Time Period ” that the relay will remain “ON”.<br />

Relay Setpoints are entered in Minutes.<br />

See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further<br />

information.<br />

P211, 221, 231, 241, 251 = 2 (Step Time)<br />

Relay Setpoint 1 is entered in values of Measurement Units (P104)<br />

See the appropriate relay function tables (P211, 221, 231, 241, 251) for further<br />

information.<br />

P214, P224, P234, P244, P254 Relay Setpoint 2<br />

P211, 221, 231, 241, 251 =1 (Time)<br />

This parameter determines the “Cycle Time ” for the operation of the relay.<br />

See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further<br />

information.<br />

P211, 221, 231, 241, 251 = 2 (Step Time)<br />

Relay Setpoints are entered in Seconds to set Drive Period, the time that the<br />

relay will remain ON<br />

See the appropriate relay Function tables (P211, 221, 231, 241, 251) for further<br />

information.<br />

Page 104